Harrington Signal IS803 User Manual
Harrington Signal Sensors
![background image](/manuals/591939/1/background.png)
I-Spy Smoke & Heat Detectors
Installation Instructions
General
These instructions apply to the I-Spy detector base IS804, to variants of this base and
to the associated ranges of UL listed I-Spy detectors which are listed overleaf.
Installation
These products must be installed in accordance with the applicable NFPA standards,
local codes and jurisdictional authorities. Failure to follow these instructions may result
in failure of the detectors to report an alarm condition. Harrington Signal Inc. is not
responsible for detectors which are improperly installed, maintained and tested.
Before installing these products check the continuity, polarity and insulation resistance
of all wiring. Check that siting is accordance with the fi re system drawings and conforms
to all applicable local codes such as NFPA 72.
Use 3" octagonal box for direct connection to the base. 4" octagonal and 4" square
boxes may be used with proper UL listed mounting brackets. When mounting on a
wall, install 4" to 12" from the ceiling. Use 3M Weatherban 606 Non-Flammable sealing
compound (or equivalent) to seal fi eld wiring conduit opening in the electrical box,
this will reduce the stack effect. Secure the base to the electrical box with appropriate
screws. Do not overtighten the screws. The raised mark on the side of the base
indicates the direction of the detector LED when fi tted. Connect the shield, if required,
to the SHIELD terminal on the base. For information on how to set the address of each
device correctly refer to the section ‘Address Setting' overleaf.
39214-230/Issue 1
Technical Data
1
4
Detector model no
IS800
IS801
IS802
IS803
Detector type
Heat
Ionization
Photoelectric
Multisensor
Working voltage
17–28V dc
17–28V dc
17–28V dc
17–28V dc
Modulation voltage
5–9V
5–9V
5–9V
5–9V
Maximum alarm
current
3.4mA
3.5mA
3.4mA
3.5mA
Surge current
1.0mA
0.5mA
1.0mA
1.0mA
Supervisory current
500µA
500µA
400µA
500µA
Heat element rating
Mode 1 129°F (54°C)
Mode 5 212°F (100°C)
N/A
N/A
Mode 5 135°F (57°C)
Control panel
Fire Spy™ Tracker 8000
Test method
•Hair dryer
•Home safeguard
Sensitivity test
•No Climb
•Gemini 501
•Home safeguard
Sensitivity test
•No Climb
•Gemini 501
•Home safeguard
Sensitivity test
•No Climb
•Gemini 501
•Hair dryer (heat
sensor only)
Installation
temperature
Minimum 32°F (0°C)
Maximum at least
20°F (11°C) below
rating
Minimum 32°F (0°C)
Maximum 100°F
(38°C)
Minimum 32°F (0°C)
Maximum 100°F
(38°C)
Mode 1-4 Minimum
32°F (0°C)
Maximum 100°F
(38°C)
Mode 5 Minimum
32°F Maximum at
least 20°F (11°C)
below rating
© Apollo Fire Detectors Ltd 2004