HS-3100/3200 Operator’s Manual
9
2.0 Supplementary Information
2.1 Condition Codes and Zone Numbers
The History and Archive use the following formats for condition codes and zone numbering.
Condition Code
Archive Alarm List
Description
A
ALARM
Alarm
B
bypass
Bypass
C
com
Comlink
D
dupl
Duplicate Addressable Device
E
alert
Maintenance Alert
G
ground
Ground Fault
H
Hot Key Pressed
I
ilgl
Illegal Addressable Device
J
Switch
M
msng
Missing Addressable Device
N
nofire
Non-Fire/Non-Reporting
P
M.PULL
Pull Station Alarm
Q
abort
Releaser Abort
R
halt
Releaser Halt
S
spv
Supervisory
T
trbl
Trouble or Parameter Change
U
wrong
Wrong Device Type
W
WFLOW
Waterflow Alarm
A plus sign (+) refers to a new or on condition, a minus sign (-) refers to a restoral or off condition,
and an equal sign (=) refers to a one time event.
Zone Number
PPP:ZZ.SSS Format:
PPP
Control Panel Number
ZZ
Panel Zone
Panel
Zone
Description
Panel
Zone
Description
0
General Alarm
81
1st Stage Alarm
1
Initiating Circuit 1
82
2nd Stage Alarm
2
Initiating Circuit 2
83
Switch
50
Network Verify
84
Test Mode
51
Comlink 1
85
1
Erase Configuration
52
Comlink 2
86
3
Change Configuration
53
Comlink 3
87
Passcode Tamper
54
Comlink 6
88
1
Database Loaded
60
Output (bell/releaser) Supervision
89
1
Time/Date Change
61
Auxiliary Power Supervision
90
1
Hot Key Activation
64
1
Program Checksum
91
1
Memory Overflow
65
1
Database Checksum
92
1
Network Reboot
66
AC Power
93
1
New Program
67
Low Battery
94
1
Network Reboot Required who
69
1
Program Restart
95
1
Network Reboot Required why
80
2
Privilege Level