Do not apply heat directly to the cold-water inlet as it is made of plastic and will melt.
G. BOILER SUPPLY CONNECTIONS
q
WARNING: Boiler temperature must be controlled by the boiler high limit not to exceed 200°.
Failure to do so will create a hazardous installation and void the applicable limited warranties.
q
All water supply fittings on this heater are brass – do not over tighten or strip threads.
q
It is recommended to use a union as per Figures 1 and 2.
NOTE: Be sure to connect Boiler Supply Line (from the boiler) to the “HX in” fitting and Boiler
Return Line (to the boiler) to the “HX Out” fitting.
H. FILLING THE HEATER
q
Check that the temperature-and-pressure relief valve has been properly installed (mandatory
requirement).
q
Completely close the drain valve.
q
Open the highest hot water faucet to allow air to escape from piping.
q
Open the valve to the cold-water inlet and allow the heater and piping system to completely fill, as
indicated by a steady flow of water from the open faucet.
I. TPI THERMOSTAT INSTALLATION
q
Attaching TPI Thermostat to tank:
Place hole in back of TPI thermostat over immersion well. TPI thermostat should fit flush against the
tank without immersion well protruding beyond cover of TPI case. Use self-tapping screw provided
(Screw A) to attach TPI directly to the Alliance SL tank. (See TPI Diagram )
q
Inserting the Temperature Sensor:
Slide temperature sensor all the way into the immersion well – until it contacts the end.
(See TPI Diagram )
q
The sensor will measure temperature adequately by resting against the bottom of the immersion
well.
(Note: Sensor does NOT need to make intimate contact with entire well surface to work properly)
CAUTION: Sensor is soldered directly to TPI. DO NOT BEND SHARPLY OR OVERWORK.
J. TPI WIRING CONTROLS
NOTE: THE TPI CONTROL ELECTRONICS MUST BE POWERED WITH 4VAC.
q
Incoming 24VAC power must be connected to 24VAC connectors on the bottom right corner of TPI
Thermostat.
(See TPI Diagram 3)
q
The TPI 24VAC only requires 20mA, or about 0.5 Watts.
q
Connect control wiring to PUMP/TT normally open relay connections (rated for both 24V and 110V
wiring) on the bottom left corner of TPI control.
(See TPI Diagram 3)
q
TPI Wiring will vary depending on the type of boiler and valve controls in the system. Consult
attached Wiring Diagrams for appropriate wiring configuration for your system.
q
The Alliance SL water heater may operate as a separate heating zone using either the heating
system circulator and an appropriate zone valve, or a separate circulator dedicated for water heating.
(See Figure & ).
q
In both systems, the Alliance SL is controlled through the TPI thermostat on the heater.
(See Figures 1 & 2).
q
TPI thermostat calls for the heat when the temperature in the tank is below the set point (120°F) and
either activates a circulator or zone valve depending upon installation design.