Weidmuller ConnectPower 6.5A Power Supply User Manual
Page 3
![background image](/manuals/575649/3/background.png)
3
Output
Adjustable via trimpot located on front cover,
from 22.5 to 28.5Vdc
Surge
13A for 1 second
Unit will shutdown if surge exceeds 1 second
Overload
Automatic restart if overloaded. Unit restarts after
approximately 4 seconds.
Contacts rated 30VDC 1A or 125VAC, 1A
maximum, Form ‘C’ SPDT.
Relay is energized when power supply is
operating under normal conditions.
Maximum 2 units can be connected in parallel for
load sharing. Derate supplies to 80% capacity
(5.2A) when load sharing. Follow these directions
for correct operation.
1. Adjust the output voltage of each power supply
to the same value before connecting them in
parallel (±200mV).
2. Connect wires of the same length from each
power supply to terminal blocks.
3. Connect the load(s) at these terminal blocks.
Output Voltage
Relay Output
Load Sharing