P36E-4 Zero Clearance Direct Vent Gas Fireplace
11
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fi replace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
Back
0"
(0mm)
Side
0"
(0mm)
Floor
0"
(0mm)
NOTE: The minimum fl oor clearance must be maintained from the top surface of the carpeting, tile, etc.
Minimum Clearance from Top of Unit to:
Ceiling
from top of unit.
32"
(1016mm)
Side Wall Clearances:
Bay or Flush Front 6"*
(152mm)
Cast Faceplate
6"*
(152mm)
Kensington Front
6"*
(152mm)
Balmoral
6"*
(152mm)
Full Screen Doors
6"*
(152mm)
* Measured from Surround or Front. See the "Regency Clearances for dimensions" section.
Horizontal Vent Clearances:
Top
2"
(51mm)
Side
1-1/2"
(38mm)
Bottom
1-1/2"
(38mm)
Vertical Vent Clearances
1-1/4"
(32mm)
Alcove Clearances**:
Max.
Depth
36"
(914mm)
Min.
Width
48"
(1219mm)
Min.
Height
72"
(1829mm)
WARNING: Fire hazard is an extreme risk if these clearances are not adhered to.
The HeatWave Duct Kit and the Heat
Release Kit have different clearance
and framing requirements, check the
HeatWave
and Heat Release manual
for details.
Heat Release Kit
CLEARANCES
INSTALLATION
Barcelona & Double Screen Door Installations
To install the combination of the Barcelona front and screen doors you
must use non-combustible mantel in conjunction with the already
required framing specs for the Barcelona front. Steel studs and
non-combustible material on the facing must be adhered to.
IMPORTANT: See the "Regency Tripoli Screen Door Series Framing Note" section for framing note on Tripoli Screen Door.