I1200 Regency Wood Insert

INSTALLATION

Clearance diagram for installations

Side and Top facing is a maximum of 1.5" thick.
Floor protection must non-combustible, insulative
material with an R value of 1.1 or greater.

*

If the hearth extension is fl ush with the fl oor (F)
it must extend 19.5" in front of the body face
(E).

Note: Hearth Extension Width (G) is meas-

ured from edge of fuel door to side of
hearth.

** A non-combustible mantel may be installed

at a lower height if the framing is made of
metal studs covered with a non-combustible
board.

MASONRY AND FACTORY BUILT FIREPLACE CLEARANCES

The minimum required clearances to combustible materials when installed into a masonry or factory built fi replace are listed below.

Adjacent

Mantle**

Top

Side

Minimum

Minimum

Minimum

Unit

Side Wall

(to Top)

Facing

Facing

Hearth

Hearth

Hearth Side

(to Side)

(to Top)

(to Side)

Extension*

Thickness*

Extension

A

B

C

D

E

F

G

I1200S

15" (381mm) 20" (508mm)

14" (356mm) 7.375"(187mm) 16" (406mm) 1.5" (38mm)

8" (203mm)

HOW TO DETERMINE IF ALTERNATE

FLOOR PROTECTION MATERIALS ARE ACCEPTABLE

The specifi ed fl oor protector should be 3/8"
(18mm) thick material with a K - factor of
0.84.

The proposed alternative is 4" (100mm) brick
with a C-factor of 1.25 over 1/8" (3mm) mineral
board with a K-factor of 0.29.

Step (a):

Use formula above to convert specifi cation
to R-value.

R = 1/k x T = 1/0.84 x .75 = 0.893.

Step (b):

Calculate R of proposed system.

4" brick of C = 1.25, therefore

Rbrick = 1/C = 1/1.25 = 0.80

1/8" mineral board of k = 0.29, therefore
Rmin.bd. = 1/0.29 x 0.125 = 0.431

Total R = Rbrick + Rmineral board =

0.8 + 0.431 = 1.231.

Step (c):

Compare proposed system R of 1.231 to
specifi ed R of 0.893. Since proposed system
R is greater than required, the system is
acceptable.

DEFINITIONS

Thermal Conductance:

C

= Btu

= W

(hr)(ft

2

)(

o

F) (m

2)

)(K)

Thermal Conductivity:

k = (Btu)(inch) = W = Btu

(hr)(ft

3

)(

o

F) (m)(K) (hr)(ft)(

o

F)

Thermal Resistance:

R = (ft

2

)(hr)(

o

F) = (m

2

)(K)

Btu

W

Floor Protection

Please check to ensure that your fl oor protection and hearth will meet the standards for
clearance to combustibles. Your hearth extension must be made from a non-combustible
material.

Thermal fl oor protection is not required if the unit is
raised 3.5" minimum (measured from the bottom of
the stove). However, standard ember fl oor protection
is required. It will need to be a non-combustible mate-
rial that covers 16" (406 mm) in the US and 18" (450
mm) in Canada to the front of the unit and 8" (200
mm) to the sides.

If the unit is not raised, thermal fl oor protection required
is 18" (450 mm) in the US and Canada.