Hsk cable glands for special applications, Rohs, Hsk-mz / hsk-mz-pvdf metr., metr.-elongated – Northern Connectors Hummel Cable Glands - for Special Applications (HSK Special) User Manual
Page 18
![background image](/manuals/569495/18/background.png)
54
AG
H
GL
M 12 x 1,5
3 – 6,5
6,5
26
14
1.690.1200.50
1.669.1200.50
10
1.690.1200.30
M 16 x 1,5
4 – 8
6
28
17 / 19
1.690.1600.50
1.669.1600.50
10
1.690.1600.30
M 16 x 1,5
6 – 10
6
30
20
1.690.1611.50
1.669.1611.50
10
1.690.1611.30
M 20 x 1,5
6 – 12
6
33
22
1.690.2000.50
1.669.2000.50
10
1.690.2000.30
M 20 x 1,5
10 – 14
6
33
24
1.690.2016.50
1.669.2016.50
10
1.690.2016.30
M 25 x 1,5
13 – 18
7
37
30
1.690.2500.50
1.669.2500.50
12
1.690.2500.30
M 32 x 1,5
18 – 25
8
43
40
1.690.3200.50
1.669.3200.50
12
1.690.3200.30
M 40 x 1,5
22 – 32
8
50
50
1.690.4000.50
1.669.4000.50
15
1.690.4000.30
M 50 x 1,5
32 – 38
9
51
57
1.690.5000.50
15
1.690.5000.30
M 50 x 1,5
25 – 31
9
51
57
1.690.5000.51
15
1.690.5000.31
M 63 x 1,5
37 – 44
10
52
64/68
1.690.6300.50
15
1.690.6300.30
M 63 x 1,5
29 – 35
10
52
64/68
1.690.6300.51
15
1.690.6300.31
EN
50262
RoHS
Accessories see page 73
Advice:
- Other sealing material e.g. Silicone upon request
HSK cable glands for special applications
HSK-MZ / HSK-MZ-PVDF
Metr., Metr.-elongated
O-Ring Buna-N / FPM
Protection IP 68 – 10 bar / IP 69K (NEMA 6 – 150 PSIG)
within the specified clamping range
Operating Temperature - 40 °C – 100 °C (- 40 °F – 212 °F) (PA)
- 35 °C – 150 °C (- 31 °F – 302 °F) (PVDF)
Seal Buna-N / FPM
Clamping insert Polyamide / PVDF
Material Nickel plated brass
Number Number
Number
AG GL H
HSK-MZ HSK-MZ-PVDF
GL HSK-MZ elongated
mm mm mm mm
- 40 °C – 100 °C - 35 °C – 150 °C
mm
- 40 °C – 100 °C
- 40 °F – 212 °F - 31 °F – 302 °F
- 40 °F – 212 °F
Dimensions and specifications may be changed without prior notice
See our homepage www.hummel.com
for assembling advices for maximum
cable diameters