Ventless Hood System

Installation

17

The fire extinguishing system must be operative before the electrical system will
function.

Refer to the electrical diagram included in attached to this unit or in the service
manual.

Standard Electrical Connection

This connection is for UL listed appliances supplied with a cord and a NEMA style 15-60 right angle plug.

1. Remove fire extinguisher access panel.

2. Route incoming power lines through holes located in the top of the 12”x8”x4” electrical enclosure.

3. Connect ground to the lug provided inside the enclosure.

4. Perform the applicable step below:

• For single-phase operation, connect incoming power to terminals L1 and L2 of the contactor.

• For three-phase operation, connect incoming power to terminals L1, L2 and L3 of the

contactor.

5. Replace electrical box cover and fire extinguisher access panel

6. Insert plug into receptacle located in the hood.

7. Install cover over plug.