PARTS & ACCESSORIES
Control Replacement Cross-Reference Guide
Model 7600 Boiler Control
R.W. Beckett Corporation
Mail: P.O. Box 1289, Elyria, OH 44036 ● Phone: 800-OIL-BURN (800-645-2876) ● FAX: (440)327-1064
R.W. Beckett Canada Ltd.
Unit 3 - 430 Laird Road, Guelph, Ontario, Canada N1G 3X7 ● Phone: 800-665-6972 ● FAX: (519)763-5656
www.beckettcorp.com
Table 1 - Direct Replacements
Honeywell
Beckett Replacement
Notes
L8124A (All)
L8124C (All)
7600A
7600 outputs are not rated for 240 VAC.
L7124A (All)
L7124C (All)
L7148A (All)
L7224A (All)
L7224C (All)
L7224U (All)
L7248A (All)
L7248C (All)
7600A
The 7600 has no Honeywell EnviraCOM
TM
Communications port. The diagnostic LED
lights are replaced by the 7600’s display.
L8148A (All)
7600A
7600 outputs are not rated for 240 VAC. B1 terminal on 7600 utilizes a 1/4” quick
connect. Set low limit on 7600 to OFF.
L8124E 1016
L8148E 1265
7600B
7600 outputs are not rated for 240 VAC. B2, TW and TR terminals replace TV, T and Z,
respectively.
L8124M (All)
7600A
For replacement with the 7600: Turn low limit off so the circulator is controlled directly by
the thermostat and ZC is constantly powered.
L8151A
7600A
7600 outputs are not rated for 240 VAC. Remote mount sensor cable needed (Part No.
52120)
Hydrolevel
Beckett Replacement
Notes
3100
7600B
Not a suitable replacement if Low Water Cutoff (LWCO) functionality is used.
3150
7600A
Carlin
Beckett Replacement
Notes
90524A
7600A
Make sure 7600 outputs do not exceed 7.4A. Available operating limit and differential
ranges are not equivalent.
White Rodgers
Beckett Replacement
Notes
11C15-11
7600A
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
Available operating limit and differential ranges may not be equivalent.
11C30-3
11B54-4
8B48A-217
11C61-12
Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600.
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
8F48A-351
8B43A-601
7600B
More on
Back
Features & Benefi ts
Beckett HeatManager
TM
dynamic temperature reset
Energy saving through circulator-off delay
Priority override for domestic hot water
Freeze resistance
2N1 self checking sensor w/ Low Water Cut-off
Cycle history diagnostic information
Backlit LCD screen with programming touch pad
Reduce inventory through universal design
Backlit LCD screen with programming touch pad
Built-in power disconnect switch (optional)
Oil and gas offerings available
Cold-Start compatible