beautypg.com

Specifications – APG IRU-3000 datasheet User Manual

Page 2

background image

2

Automation Products Group, Inc.
1025 West 1700 North

Tel. 1/888/525-7300

Logan, UT 84321 USA

Fax 1/435/753-7490

w w w . a p g s e n s o r s . c o m

s a l e s @ a p g s e n s o r s . c o m

IRU-2000/3000 Ultrasonic Level Sensors

APG

Automation Products Group, Inc.

®

Specifications

Model

IRU-200x

IRU-212x/222x/233x

IRU-313x/323x

Operating Range

1 to 25 ft. (0.3 to 7.6 m)

1 to 25 ft. (0.3 to 7.6 m)

1.25 to 35 ft. (0.38 to 10.67 m)

Available Outputs

(1) solid state relay

4-20 mA with (2) NPN trips

4-20 mA with (2) NPN trips

4-20 mA with (2) NPN trips

Isolated 4-20 mA

Isolated 4-20 mA

Isolated 4-20 mA

RS-485 with (1) NPN trip

RS-485 with (1) NPN trip

Supply Voltage

24 VDC*

24 VDC*

24 VDC*

Total Current Draw

80 mA @ 24 VDC

80 mA @ 24 VDC

80 mA @ 24 VDC

Maximum Rated Power

2.5 W

2.5 W

2.5 W

Housing

ABS with UV inhibitor

PVC

PVC

Mounting

Surface mount, (4) screws

2 and 3 NPT

3 NPT

2 in. Teflon

®

faced flange

3 in. Teflon

®

faced flange

3 in. sanitary 3A flange

Transducer Type

Ceramic

Ceramic

Ceramic

Ratings

NEMA 4X

NEMA 4X

NEMA 4X

Approvals

Models 2002, 2003 & 2005:

Models 2125 & 2225:

Models 3135 & 3235:

CSA C/US General Purpose Rating

Class 1, Div. 2, Groups A,B,C,D

Class 1, Div. 2, Groups A,B,C,D

All Models:

All Models:

CSA C/US General Purpose Rating

CSA C/US General Purpose Rating

Response Time

Programmable (20 ms minimum)

Programmable (20 ms minimum)

Programmable (20 ms minimum)

Sample Rate

Programmable (1-22 Hz)

Programmable (1-22 Hz)

Programmable (1-22 Hz)

Resolution

0.1 in. (2.5 mm)

0.1 in. (2.5 mm)

0.1 in. (2.5 mm)

Accuracy

(with no temperature gradient)

±0.25% of detected range

±0.25% of detected range

±0.25% of detected range

Adjustments

RS-232 with RST module;

RS-232 with RST module

RS-232 with RST module

potentiometer adjustments

available on select models

Operating Temperature

-40 to 140°F (-40 to 60°C)

-40 to 140°F (-40 to 60°C)

-40 to 140°F (-40 to 60°C)

Temperature Compensation

Internal

Internal

Internal

Beam Pattern

9° off axis

9° off axis

9° off axis

Connections

IRU-2002 & 2003:

(6) conductor cable

(6) conductor cable

(6) pin terminal strip

(6 ft. (1.8 m) standard length)

(6 ft. (1.8 m) standard length)

IRU-2004 & 2005:

(6) conductor cable

(6 ft. (1.8 m) standard length)

Frequency

69 kHz

69 kHz

43 kHz

* The sensor will operate from 12-28 VDC, but the sensor performance will be diminished if the voltage is less than 24 VDC. A minimum of 14 VDC is
required to program the sensor using the RST module.
Specifications are subject to change without notice.

This manual is related to the following products: