beautypg.com

Dcu-1100 ultrasonic level sensors, Dimensions — in./mm, Wiring – APG DCU-1100 datasheet User Manual

Page 2: Ordering information, Specifications

background image

2

Automation Products Group, Inc.
1025 West 1700 North

Tel. 1/888/525-7300

Logan, UT 84321 USA

Fax 1/435/753-7490

w w w . a p g s e n s o r s . c o m

s a l e s @ a p g s e n s o r s . c o m

DCU-1100 Ultrasonic Level Sensors

APG

Automation Products Group, Inc.

®

Dimensions — in./mm

Wiring

DCU-1100

Red

+ 24 VDC

Black

– VDC

Green

Clock synch

White

Digital pulse width

Blue

Relay 1 common

Grey

Relay 1 normally open

Purple

Relay 2 common

Brown

Relay 2 normally open

Orange

4-20 mA output

Yellow

4-20 mA ground

Ordering Information

DCU – 110

Mounting Option
4

3 NPT

8

3 in. 150 lb. flange

1/2" NPT

DCU-1108

1/2" NPT

3" NPT

DCU-1104

DCU-1611

1/2" NPT

2" NPT

1" NPT

DCU-1621

1/2" NPT

2" NPT

DCU-1633

2" Sanitary

3A Flange

1/2" NPT

DCU-7070

DCU-7110

1" NPT

2" NPT

DCU-7210

1" NPT

7.5

190.5

2.35

59.7

1.30

33

6.00

152.4

6.00

152.4

3.75

95.3

4.0

101.6

2.25

57.2

3.50

88.9

8.00

203.2

3.75

95.3

5.50

139.7

5.50

139.7

12.5

317.5

12.7

322.6

2.35

59.7

2.35

59.7

3.5

88.9

2.35

59.7

3.5

88.9

5.25

133.4

For information on ultrasonic sensing
accessories, see www.apgsensors.com

Specifications

Operating Range: 2 to 50 ft. (0.6 to 15.2 m)
Output: (2) solid state relays and 4-20 mA
Supply Voltage: 24 VDC*
Total Current Draw: 110 mA @ 24 VDC
Maximum Rated Power: 3 W
Housing: PVC
Mounting: 3 NPT or 3 in. 150 lb. flange
Transducer Type: DCU-1104: ceramic, PVC faced

DCU-1108: ceramic, Teflon

®

faced

Ratings: NEMA 4X
Approvals: FM Class I, Div. 2
Response Time: Programmable (120 ms minimum)
Sample Rate: Programmable (8-0.125 Hz)
Resolution: 0.1 in. (2.5 mm)
Accuracy

(with no temperature gradient)

: ±0.25% of detected range

Adjustments: Integrated keypad
Operating Temperature: -30 to 140°F (-34 to 60°C)
Temperature Compensation: Internal
Beam Pattern: 9° off axis
Connections: (10) conductor cable (6 ft. (1.8 m) standard length)
Frequency: 42 kHz

* The sensor will operate from 12-28 VDC, but the sensor performance will be diminished if the

voltage is less than 24 VDC.