beautypg.com

APG LFE Series user manual User Manual

Page 6

background image

LFE Series

Rev. A1, 4/07

6

Automation Products Group, Inc.

APG...Providing tailored solutions for measurement applications

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

• Installation Location

Locate the LFE at the position where the liquid level variation will actually

make contact with it. DO NOT locate near liquid inlets/outlets. If there is
turbulence, use a time delay relay to dampen the switch action.

LFE-XXX-XA (Switch closes as level falls), see Figure A
LFE-11R

LFE-12R

LFE-11P

LFE-12P

Close as level falls

18

28

15

23

Open as level rises

16.5

26.5

13.5

21.5

LFE-XXX-XB (Switch closes as level rises), see Figure B
LFE-11R

LFE-12R

LFE-11P

LFE-12P

Close as level rises

17

26

14

25

Open as level falls

18.5

27.5

15.5

26.5

Figure A