Troubleshooting, Reparacion de averias – Briggs & Stratton 071019 User Manual

Page 12

background image

12

BRIGGSandSTRATTON.COM

Troubleshooting

Problem

Cause

Correction

Automatic transfer switch does not
transfer to generator

1. Generator breaker open.

2. Generator voltage not acceptable.

1. Reset generator circuit breaker.

2. Refer to generator manual.

Automatic transfer switch does not
transfer to utility

1. Utility disconnect breaker open

(Models 071020 & 071021 only).

2. Service disconnect breaker open.

3. Utility voltage not acceptable.

1. Reset utility disconnect breaker

(Models 071020 & 071021 only).

2. Reset service disconnect breaker.

3. Wait for utility voltage to return to

normal.

Generator is still running after switch
transfers to utility power

Engine cool down period.

Engine should stop after 1 minute.

Supervised loads (air conditioner, etc.)
are not operating when generator is
supplying power

1. A-A or B-B contacts not operating

correctly.

2. Too much load on generator.

3. Current transformer not connected.

4. Broken current transformer.

1. Check A-A or B-B contacts for

proper operation and/or check
control wiring to external load.

2. Decrease load to generator.

3. Plug CT connectors into control

board.

4. Contact local Briggs & Stratton

Power Products service center.

Generator is still running after utility
power is restored

1. Minimum engine run time has not

elapsed.

2. Fuse(s) in transfer switch is

defective.

1. Wait five minutes for transfer

switch to retransfer to utility power.

2. Check fuse(s) and replace if

necessary.