Troubleshooting, Reparacion de averias, Dépannage – Briggs & Stratton 71013 User Manual
Page 13

11
Troubleshooting
Problem
Cause
Correction
Supervised loads (air conditioner, etc.)
are not operating when generator is
supplying power
1.
AC1A-AC2B contacts not operating
correctly.
2.
Too much load on generator.
3.
Current transformer not connected.
4.
Broken current transformer.
5.
Status LED stays lit constantly.
1A. Check AC1A-AC2B contacts for
proper operation.
B. Check control wiring to external
load.
C. Check harness between boards is
properly connected.
D. Check that there is 24 VAC to one of
the terminals.
E. Be sure 5 minute lock out has
elapsed.
F. Be sure air conditioner start time
delay has elapsed.
2.
Decrease load to generator.
3.
Connect current transformer.
4.
Replace current transformer.
5.
Contact an authorized service
center.
See also other documents in the category Briggs & Stratton Generators:
- 30348 (48 pages)
- PowerBoss 30227 (32 pages)
- 01893 (52 pages)
- 1653 (48 pages)
- 204730GS (96 pages)
- 30372 (5 pages)
- 030235-02 (6 pages)
- 40229 (56 pages)
- BSP3200 (4 pages)
- PowerBoss 30220 (6 pages)
- PowerBoss 30230 (28 pages)
- 203985GS (84 pages)
- 206494GS (48 pages)
- 30204 (28 pages)
- 30424 (6 pages)
- 030244-02 (6 pages)
- Elite Series 30209 (36 pages)
- 030235-01 (6 pages)
- 30334 (6 pages)
- 7000 RATED WATTS 040220A (80 pages)
- Elite 01532-3 (48 pages)
- Powerlink On-Board Generator System (4 pages)
- 40273 (12 pages)
- 12KW (52 pages)
- 76001 (5 pages)
- 30246 (44 pages)
- Elite 030211 (6 pages)
- PRO6500 (56 pages)
- 1933 (8 pages)
- 190477GS (40 pages)
- 40275 (7 pages)
- 30254 (6 pages)
- 030249 (28 pages)
- 40266 (12 pages)
- 01970 (28 pages)
- 040212 (56 pages)
- PowerBoss 30255 (5 pages)
- 040234-1 (7 pages)
- 40G700 (20 pages)
- 01532-2 (60 pages)
- 40212 (7 pages)
- PowerBoss 30221 (6 pages)
- 01918-0 (40 pages)
- 040226-1 (7 pages)
- 40226 (7 pages)