MAINTENANCE SCHEDULES

USE AND MAINTENANCE
SHALL BE IN ACCORDANCE
WITH THE STANDARD FOR
VENTILATION CONTROL
AND FIRE PROTECTION OF
COMMERCIAL COOKING
OPERATIONS
, N.F.P.A 17A
& N.F.P.A. 96 (current
editions).

DANGER

FIRE
HAZARD


FAILURE TO PROPERLY
CLEAN AND MAINTAIN THIS
EQUIPMENT CAN
CAUSE A FIRE. AN
UNCONTROLLED FIRE CAN
CAUSE SERIOUS INJURY,
DEATH AND/OR PROPERTY
LOSS.


NOTE: A signed and dated
VENTILATOR HOOD
MAINTENANCE LOG must
be maintained on the
premises, and shall be
available for inspection by the
authority having jurisdiction.
See pages 26 & 27.


IMPORTANT: Parts used
for the Ansul® fire
suppression system are not
serviceable by the owner /
operator.
Procedures for
servicing fire suppression
equipment are described in:
ANSUL® R-102 SYSTEM
DESIGN, INSTALLATION,
RECHARGE AND
MAINTENANCE MANUAL
(Ansul® #418087-05).

1. 6-MONTH MAINTENANCE (MUST BE PERFORMED BY AN

AUTHORIZED ANSUL® DISTRIBUTOR ONLY):


a.

Inspect and test total operation including FIRE DAMPER and

all

SAFETY

INTERLOCKS.


b.

All FIRE SUPPRESSION SYSTEM actuation components

including MANUAL PULL STATION and any REMOTE

MANUAL PULL STATION must be inspected for proper

operation in accordance with the maintenance schedule

published

in

ANSUL® R-102 SYSTEM DESIGN,

INSTALLATION, RECHARGE AND MAINTENANCE MANUAL

(Ansul® #418087-05).


c.

The FIRE SUPPRESSION SYSTEM FUSIBLE LINKS must be

inspected. NOZZLES and MANUAL PULL STATION must be

cleaned

in

accordance

with

ANSUL® R-102 SYSTEM

DESIGN,

INSTALLATION,

RECHARGE AND MAINTENANCE

MANUAL

(Ansul® #418087-05).


d.

The FIRE SUPPRESSION AGENT TANK, PIPING and

FLEXIBLE TUBING must be INSPECTED.


2. 12-YEAR MAINTENANCE: (MUST BE PERFORMED BY AN

AUTHORIZED ANSUL® DISTRIBUTOR ONLY):


a.

The FIRE SUPPRESSION AGENT TANK and ¼” FLEX HOSE

must be HYDROSTATICALLY TESTED, and the FIRE

EXTINGUISHING

AGENT

must

be REPLACED in accordance

with the maintenance schedule published in ANSUL® R-102

SYSTEM (STANDARD UL 300 LISTED).

b.

The FUSIBLE LINKS in plenum and damper must be

REPLACED. This maintenance to be performed by qualified

Ansul® service personnel only.