Troubleshooting – Briggs & Stratton 01917-0 User Manual
Page 11
11
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner’s Manual
TROUBLESHOOTING
Problem
Cause
Correction
Automatic transfer switch does
not transfer to generator
1.
Generator breaker open.
2.
Generator voltage not acceptable.
1.
Reset generator circuit breaker.
2.
Refer to generator manual.
Automatic transfer switch does
not transfer to utility
1.
Main distribution panel breaker
open.
2.
Utility voltage not acceptable.
1.
Reset main distribution panel
breaker.
2.
Wait for utility voltage to return to
normal.
Generator is still running after
switch transfers to utility power
Engine cool down period.
Engine will stop after 1 minute.
Generator is still running after
utility power is restored
1.
Minimum engine run time has not
elapsed.
2.
Fuse(s) in transfer switch is
defective.
1.
Wait five minutes for transfer
switch to retransfer to utility
power.
2.
Check fuse(s) and replace if
necessary.