K series atmospheric gas indirect water heaters – Bryan Boilers K350 User Manual

Page 2

background image

Bryan Boilers

K SERIES ATMOSPHERIC GAS

INDIRECT WATER HEATERS

Form # >> 1675

Date >> 5/11/2004

BOILER MODEL

K350

K400

MBH

3,500

4,000

(KW)

1,025.5

1,172.0

MBH

2,800.0

3,200.0

(KW)

820.4

937.6

HP

84

96

(KW)

823

941

INCHES

1.50

1.50

(CM)

3.81

3.81

NUMBER OF TUBES

53

59

PRESSURE VESSEL

GAL

146

160

(L)

552.6

605.6

SQ FT

424

480

(SQ M)

39.4

44.6

INDIRECT HEAT EXCHANGER

INCHES

105

115

(CM)

267

292

LBS

6,040

6,555

(KG)

2,739.7

2,973.3

LBS

4,820

5,220

(KG)

2,186.4

2,367.8

RELIEF VALVE TYPICAL - 30 PSIG (206.8 KPA)

QUANTITY

1

1

INCHES

2 x 2½

2 x 2½

(CM)

5.08 x 6.35

5.08 x 6.35

MBH

5,250

5,250

(KW)

1,538.2

1,538.2

RELIEF VALVE TYPICAL - 125 PSIG (861.8 KPA)

QUANTITY

1

1

INCHES

1¼ x 1¼

1¼ x 1¼

(CM)

3.17 x 3.17

3.17 x 3.17

MBH

5,370

5,370

(KW)

1,573.4

1,573.4

INPUT

HEATING SURFACE

OPERATING WEIGHT

SHIPPING WEIGHT

UTF(###)-(##)-(#)

VOLUME

TUBE DIAMETER

BOILER HORSEPOWER

OUTPUT*

SIZE

CAPACITY-TOTAL

SIZE

CAPACITY-TOTAL

* Output based on nominal 80% of input. Actual combustion efficiencies may vary.
(###) - - Indicates number of passes.
(##) - - Indicates number of tubes.
(#) - - Indicates length of exchanger.