Crystal-clear controller signal out to 4000 feet

(1219.2 m).

»

Opto-isolation available.

»

Can be configured for two- or four-wire

and half- or full-duplex operation.

»

Connect to your RS-485 network via RJ-45

modular connectors or screw-block terminals.

FEatuRES

BLACK BOX

®

RS-485 Repeaters extend your RS-485

communications beyond the 4000-foot limit. Even located 5000 feet
from your master device, they’ll take your RS-485 communications
signals and shoot them another 4000 feet.

Great for connecting multiple RS-485 segments in different

buildings or rooms, the repeaters enable you to add more devices
to your network—up to 32 more units per repeater.

They support either 2- or 4-wire applications, in full- or half-duplex

operation. Plus, the

RS-485 Repeaters

come with a 4-screw terminal

block, RJ-45 connectors, and an edge card connector, so they fit right
in with any RS-485 wiring scheme.

To protect your lines from ground loops and other electrical

problems, order the

RS-485 Repeater

with Opto-Isolation (IC158A).

Ideal for industrial applications, it isolates one segment of your
extended network from problems that may arise on another segment.

Inside the opto-isolated repeater, optical isolation circuitry converts

electrical signals to light and back again to keep signal noise and
ground loops from crossing between segments of your RS-485
installation. Electrical noise from your factory floor won’t affect office
communications, and the difference in ground potential between
buildings won’t damage your sensitive equipment.
Simple to install and configure.

Just set internal jumpers and switches to match the cabling and

duplex operation of your application as well as to match repeater

OVERVIEW

ports for terminated and unterminated operation. Then, connect your
devices to the repeater itself, power it up, and power up the rest of
your RS-485 network.

In half-duplex mode, jumpers determine the turnaround delay for

the receiving repeater. Through these jumpers, you can configure the
delay to match the length of cables and the number of device drops in
your application.

The greater the length of your RS-485 line or the larger the

number of drops on the your network, the longer the line will remain
charged after the transmitter has been disabled.

The

RS-485 Repeaters

use three different types of delays: a turn-

around delay, a turn-ON delay, and a turn-OFF delay. The turn-ON
delay prevents the repeaters from passing along noise. It does this by
delaying the transmitter long enough to allow most noise to dissipate
before transmitting. With turn-OFF delay, the repeaters‘ transmitter
is enabled long enough for the input data to propagate though the
repeater after the sending device drops a signal.

Both repeater models have three LEDs visible through their front

panel that indicate power, carrier detect, and when a transmitter is
enabled on the RS-485 line.

NOTE: The repeaters do not feature collision detection or hardware
flow control.

T e c h S P e c S

Flow Control — Transparent

Leads Supported — Both ports: TDA, TDB, RDA, RDB

Operation — Half- or full-duplex

Speed — Transparent up to 128 kbps

CE Approval — Yes

Connectors — (2) 4-wire terminal blocks, (2) RJ-45

Indicators — Power, Carrier Detect (both ports)

Operating Environment — Temperature: 32 to 110ºF (0 to 45ºC)

Humidity: 0 to 95%, noncondensing

Power — 115 VAC, 60 Hz (230-VAC, 50-Hz version on request)

Size — 1.8"H x 5.5"W x 8.5"D (4.6 x 14 x 21.6 cm)

Item

Code

RS-485 Repeater

IC155a

RS-485 Repeater with Opto-Isolation

IC158a