Method to size ervs and hrvs, Heating and cooling load charts, Ventilator sizing – Bryant HEAT RECOVERY VENTILATOR HRVBBLHA User Manual
Page 6

6
METHOD TO SIZE ERVs and HRVs
Ventilator Sizing
Tables 1 and 2 should be used to determine the required airflow for a home. These guidelines are taken from ASHRAE 62.2--2007.
Table 1 – Ventilation Air Requirements, cfm
FLOOR
AREA (ft
2
)
BEDROOMS
0---1
2---3
4---5
6---7
>7
<1500
30
45
60
75
90
1501---3000
45
60
75
90
105
3001---4500
60
75
90
105
120
4501---6000
75
90
105
120
135
6001---7500
90
105
120
135
150
>7500
105
120
135
150
165
Table 2 – Ventilation Air Requirements, L/s
FLOOR
AREA (m
2
)
BEDROOMS
0---1
2---3
4---5
6---7
>7
<139
14
21
28
35
42
139.1---279
21
28
35
42
50
279.1---418
28
35
42
50
57
418.1---557
35
42
50
57
64
557.1---697
42
50
57
64
71
>697
50
57
64
71
78
HEATING AND COOLING LOAD CHARTS
Although the ventilators process the outside air before it enters the home, additional heating and cooling loads need to be considered.
HEATING LOAD BTUH
Outside
Temp °F
Heating Load (Btuh) @
Inside Design Temp 72°F
ERV1150
ERV1200
HRV1150
HRV1250
–25
5186
8143
6636
10603
–20
4919
7723
6294
10057
–15
5075
7967
5952
9510
–10
4783
7509
5610
8964
–5
4491
7051
5268
8417
0
4200
6594
4925
7871
5
4234
6647
4583
7324
10
3918
6151
4241
6777
15
3958
6214
3899
6231
20
3611
5669
3557
5684
25
3264
5124
3215
5138
30
2916
4579
2873
4591
35
2569
4034
2531
4045
40
2222
3489
2189
3498
The heating load chart shows the heating loads in Btuh for a range
of winter design temperatures for each model of ventilator.
EXAMPLE: The heating design temperature for Little Rock, AR is
20_F. The additional heating load of the ERVBBLHA1200 at
20_F is 559 Btuh. This additional load should be taken into
consideration when sizing the heating equipment.
COOLING LOAD BTUH
Outside
Enthalpy
Btu/lb
Cooling Load (Btuh) @ Inside Design Temp
72°F and 50% Relative Humidity
ERV1150
ERV1200
HRV1150
HRV1250
30
380
640
670
1071
31
618
1040
1090
1741
32
855
1441
1509
2411
33
1093
1841
1928
3080
34
1331
2241
2347
3750
35
1568
2641
2766
4419
36
1806
3041
3185
5089
37
2043
3441
3604
5759
38
2281
3842
4023
6428
39
2519
4242
4442
7098
40
2756
4642
4861
7767
41
2994
5042
5280
8437
42
3231
5442
5699
9107
The cooling load chart shows loads in Btuh as well. To use the
cooling load chart, first find the design enthalpy from a
psychrometric chart using the design dry bulb and wet bulb
temperatures. The cooling load can then be found for a range of
enthalpies for each ventilator.
EXAMPLE: The design dry bulb temperature for Miami is 90_F
and the average wet bulb at that temperature is 77_F. Using the
psychrometric chart, the enthalpy is about 40.5 Btu per pound
(Btu/lb) of dry air, which would round up to 41 Btu/lb dry air. In
the left column, at 41 Btu/lb dry air, the ERVBBLHA1200 has an
additional cooling load of 5042 Btuh, while the HRV1150CFM
unit has an additional cooling load of 8437 Btuh.
ER
V
/HR
V