The manometer port permits temporary installation of a
manometer (Figure 5), to ensure that the engine receives
the correct fuel pressure to operate efficiently throughout
its operating range.

NOTE: A digital manometer, P/N 19495, is available at your
local Briggs and Stratton Power Products service center.

When the initial test runs are completed, the manometer is
removed and the port is plugged. A typical final fuel
connection assembly is shown in Figure 6.

Fuel Consumption

See Figure 7 for fuel supply requirements at half and full
load for both natural gas and LP vapor.

13

Briggs & Stratton Power Products Standby Generator

Installation, Start-Up and Owner’s Manual

• Before placing the Standby Generator into service, the fuel

system lines must be properly purged and leak tested.

• NO leakage is permitted.

Propane and Natural Gas are extremely
flammable and explosive.
Fire or explosion can cause severe burns or
death.

WARNING

Figure 6 — Completed Fuel Connections

From Fuel

Supply Line

To Standby

Generator

Figure 5 — Temporary Manometer Installed

Natural Gas*

LP Vapor**

1/2 Load

Full Load

1/2 Load

Full Load

80

137

33

56

* = Natural Gas is in cubic feet per hour

** = LP Vapor is in cubic feet per hour

Figure 7 — Fuel Supply Requirements