BRYAN ELECTRIC INDIRECT WATER HEATER RATINGS AND DIMENSIONS — in (cm)

Heat

Recovery

Boiler

Power Panel

Boiler Coil

Exchanger Element

Model

Input Output

Capacity

Dimensions

Dimensions

Inlet & Inlet &

Removal Removal

Shipping

KW

MBH

(GPH)

length width height

208-230/3/60 380, 460/575

Outlet

Outlet

I J

Clearance

Clearance

Weight

40°-140°F

A

B

C

D

E

D

E

F

&

G

H

K

L

lbs. (kg)

BE-30-WT

30

98.3 117 48 20 32 30 36 20 24

2 1-1/2

26 17 26

30

840

(122)

(51)

(81)

(76)

(91)

(51)

(61)

(5)

(3.8) (66) (43) (66)

(77)

(373)

BE-45-WT

45 147.4 176

48 20 32 30 36 20 24

2

2 26 17 26

30

870

(122)

(51)

(81)

(76)

(91)

(51)

(61)

(5)

(5.08) (66) (43)

(66)

(77)

(387)

BE-60-WT

60 196.6 235

48 20 32 30 36 20 24

2

2 26 17 26

30

900

(122)

(51)

(81)

(76)

(91)

(51)

(61)

(5)

(5.08) (66) (43)

(66)

(77)

(400)

BE-90-WT

90 294.8 354

48 25 40 30 36 20 30

3

2 32 20 26

30 1070

(122)

(71)

(102)

(76)

(91)

(51)

(73)

(8)

(5.08) (79) (51)

(66)

(77)

(476)

BE-105-WT

105 344.0

413

48 28 40 30 48 20 30

3

2 32 20 26

30 1115

(122) (71) (102) (76) (122) (51) (76)

(8) (5.08) (79) (51)

(66)

(77)

(496)

BE-120-WT

120 393.1

472

48 28 40 30 48 20 30

3

2 32 20 26

30 1170

(122) (71) (102) (76) (122) (76) (91)

(8) (5.08) (79) (51)

(66)

(77)

(521)

BE-135-WT

135 441.0

531

48 28 40 30 66 30 36

3 2-1/2

32 20 26

30 1370

(122) (71) (102) (76) (168) (76) (91)

(8) (6.35) (79) (51)

(66)

(77)

(610)

BE-150-WT

150 491.4

590

48 28 40 30 66 30 36

3 2-1/2

32 20 26

30 1390

(122) (71) (102) (76) (168) (76) (91)

(8) (6.35) (79) (51)

(66)

(77)

(618)

BE-165-WT

165 539.1

649

48 28 40 30 66 30 36

3 2-1/2

32 20 56

30 1420

(122) (71) (102) (76) (168) (76) (91)

(8) (6.35) (79) (51) (142)

(77)

(632)

BE-180-WT

180 589.7

708

48 28 40 30 66 30 36

3 2-1/2

32 20 56

30 1470

(122) (71) (102) (76) (168) (76) (91)

(8) (6.35) (79) (51) (142)

(77)

(654)

BE-195-WT 195 637.2 767 48 28 40 30 66 30 48

3 2-1/2

32 20 56

30 1800

(122) (71) (102) (76) (168) (76) (122)

(8) (6.35) (79) (51) (142)

(77)

(801)

BE-210-WT

210 688.0

826

76 28 40 N/A N/A 30 48

3 2-1/2 32 20

56

55

2600

(193)

(71)

(102)

(76)

(122)

(8)

(6.35) (79) (51) (142)

(140) (1157)

BE-240-WT

240 789.5

948

76 28 40 N/A N/A 30 48

3 2-1/2 32 20

56

55

2650

(193)

(71)

(102)

(76)

(122)

(8)

(6.35) (79) (51) (142)

(140) (1180)

BE-270-WT

270 884.5 1,062 76 28 40 N/A N/A 30 66

3 2-1/2 32 20

56

55

2700

-

(193)

(71)

(102)

(76)

(168)

(8)

(6.35) (79) (51) (142)

(140) (1202)

BE-300-WT

300 982.0 1,180 76 28 40 N/A N/A 30 66

3 2-1/2 32 20

56

55

2750

(193)

(71)

(102)

(76)

(168)

(8)

(6.35) (79) (51) (142)

(140) (1224)

BE-330-WT

330 1,081.1 1,298

76 28 40 N/A N/A 30 66

3 2-1/2 32 20

56

55

2800

PLAN VIEW

Size range: 30-330 KW (98,300 to 1,081,100 BTUH) with the following voltage options:

30 KW to 120 KW — 240 volt/1 phase; 30 KW to 180 KW — 208 or 240 volts/3 phase; 30 KW to 330 — 460 or 480 volts/3 phase.

Equipment furnished: Combination boiler thermometer and pressure gauge, low water cutoff, operating temperature control, high limit tem-
perature control, indirect heat exchanger, automatic boiler fi ll valve, boiler relief valve, boiler drain cock, magnetic contactors, pilot switch,
power panel, insulated jacket and expansion tank. All equipment installed and wired. Expansion tank (shipped loose). A fused disconnect
switch to be furnished by installer.

When ordering: Please specify model, KW, type of system (tank or tankless). Initial and fi nal temperature water required, water fl ow rate (gal./
hr. or gal./min.), electrical characteristics (volts, phase, cycles), optional equipment or special requirements. Refer to BE Series brochure No.
3600 for further information.