Appendix b, Ground pole installation (1.2m system), 2m antenna survival windloads at 125 mph velocity – Andrew 960 User Manual

Page 5: Pole specifications, Pier foundations deep frost line foundations

background image

GROUND POLE INSTALLATION (1.2m System)

4

MIN.

DIA.

d

d

MIN.

DIA.

ANT

2.88" or

3.00" O.D.

2.88" or

3.00" O.D.

40"

C

L

72"

35.8"

35.8"

increased,

72"

40.9"

50" depth may be

will increase

length of rebar

concrete and

accordingly.

2"

2"

50"

NOTE:

#3 REBAR x DIA. OF PIER, INSERT

FROST LINE

#3 REBAR x

DIA. OF PIER

INSERT THRU HOLE

IN TUBE & CENTER

AT 90

o

APART

(SEE NOTE)

(4)#3x24"MIN.

BELOW

THRU HOLE IN TUBE & CENTER

1" to 2"

WATER RUN OFF

GRADE

SLOPE FOR

BELOW

FROST LINE

APPROX.

1" to 2"

SLOPE FOR

(SEE

NOTE)

GRADE

WATER RUN OFF

GROUND

ANT

WIND VEL.

DIM “d”

CONC VOL.

DIM “d”

CONC VOL.

DIM “d’

CONC VOL. DIM “d” CONC VOL. POLE

80 MPH

8”

1.3

13”

3.4

8”

1.6

10”

2.5

“A” or

90 MPH

10”

2.0

16”

5.1

8”

1.6

12”

3.6

“B”

1.2M

100 MPH

12”

2.9 18”

6.5 8”

1.6

13”

4.2

“B” or

LFL

110 MPH

14”

3.9

21”

8.8

10”

2.5

16”

6.4

“C”

125 MPH

17”

5.8

24”

11.5 12”

3.6

19”

9.0

“D”

POLE SPECIFICATIONS:

Ground Pole “A” = 2.88 O.D. x .154 Wall (Sch 40) x 72” ASTM A53 or A501 Pipe
Ground Pole “B” = 3.00 O.D. x 9 Ga. (.148 Wall) x 72” Steel - CM PN 611685101
Ground Pole “C” = 2.88 O.D. x 2.88 O.D. x .276 Wall (Sch 80) x 72” Steel ASTM A53 or A501 Pipe
Ground Pole “D” = 3.00 O.D. x .250 Wall x 72” Steel ASTM 120 Mech Tubing

NOTE:
Pole “B” is supplied from factory powder painted and with hole for #3 rebar and grounding screw.

Poles “A”, “C” and “D” are not supplied and must be field drilled ⁵⁄₈” dia. for #3 rebar and drilled .218

for ¹⁄₄-20 self tapping grounding screw and galvanized or painted for protection.

1 - Pole and foundation design based on the following criteria:

a) Uniform building code exposure B or C and 1.5 stability factor.
b) Vertical soil pressure of 2000 pounds per square foot.
c) Lateral soil pressure of 400 pounds per square foot.
d) Concrete compressive strength of 2500 pounds per square inch in 28 days.

2 - CAUTION - The foundation design shown does not represent an appropriate design for any specific locality since soil conditions vary

and may not meet design criteria given in Note 1. You should consult a local professional engineer to determine your soil conditions
and appropriate foundation.

Exposure “B”

Exposure “C”

Exposure “B”

Exposure “C”

PIER FOUNDATIONS

DEEP FROST LINE FOUNDATIONS

Bubble
Level

Ground Pole
Must Be
Vertical In
All Directions
Within .19 Inches
At Top (0.3ß)

13

Mo Based on 40.9" (1039 mm) from Mounting Surface of Center Line of Antenna

Values shown represent maximum forces for any wind direction and
include 1.5 Fs. Height and exposure factors from uniform building code

are NOT included.

APPENDIX B

1.2m Antenna Survival Windloads at 125 MPH Velocity

BE

AM

AX

IS

MECHANICAL AXIS

(NORMAL TO ANTENNA FACE)

16.97

o

OFFSET

40.9" HEIGHT
(1039 mm)

FH

MT

FV

F

H

= Horizontal Force

F

V

= Vertical Force

M

T

= Torsional Moment

M

O

= Overturning Moment

MO

ELEVATION DEGREES

MECHANICAL

BEAM

0

17

10

27

20

37

30

47

40

57

50

67

60

77

70

87

FORCE (POUNDS)

F

H

F

V

1285

-35

1217

-257

1182

-497

1071

-711

943

-857

822

-943

686

-985

515

-762

MOMENTS (FT-LBS/N-m)

M

T

M

O

500

4,380

488

4,148

464

4,029

421

3,650

357

3,214

299

2,802

232

2,338

178

2,096