beautypg.com

Approvals – Pfannenberg PATROL PA X 1 Series User Manual

Page 7

background image

085 501 944k

30303-004k

7

Approvals

Approvals (valid for marked equipment)

Construction Product
Directive
(89/106/EWG)

PA 1: VdS 0786-CPD-21182

PA X 1-05: 0786-CPD-21220

PA 1

PA X 1-05

Options

–SSM

Rated voltage

24 – 48V DC

24V DC

48V DC

Operating voltage range
acc. to EN54-3, EN54-23

18V – 57V

Option: -SSM (18V – 30V)

18 - 30V

40 - 57V

Lens colours of beacon

-

red, clear

Tone

2

15
60

104
131
146

Compliant with the Construction Product Directive (89/106/EWG)

1200Hz-500Hz (Saw tooth) DIN/PFEER P.T.A.P.

500Hz-1200Hz (Slow whoop)

825Hz (Continuous)

660Hz (Intermittent tone)

800Hz/ 1000Hz (Alternating tone)

544Hz/ 440Hz (NF S 32-001)

Signaling area

EN54-3:

see document 30303-005-1

EN 54-23 Category O:

see document 30303-005-1

Environmental
protection class

Type B

Installation position

arbitrary

Light faces down

The test was performed using the provided diaphragm nipples and the outer fixing holes.

VdS

PA1: G 212115, PA X 1-05: G 212188
Data see Construction Product Directive (89/106/EWG)

GL

GLxxxxx (in preparation)
Environmental Category C, H, EMC1

UL, cUL


Rated

Voltage

Audible-signal Appliance

Fire Alarm Equipment

ULSZ, ULSZ7

Audible and Visual signal Appliance

General Signal Equipment

UCST, UCST7 and UEES, UEES7

PA 1

24V – 48V DC

(Fire Alarm Equipment)

12V – 48V DC

(General Signal Equipment)

x

Special application, limited operat-

ing voltage range 18 – 57V DC

x

PA 1
PA X 1-05

24V AC

115V AC
230V AC

-

x

PA X 1-05

12V DC
24V DC
48V DC

-

x

PATROL sounders and combined units PA 1/ PA X 1-05 comply with the limits for a Class B digital device, pursuant to
part 15 of the FCC Rules.

UL/ cUL specifications:

Suitable for indoor and outdoor use. Signaling area: see document 30303-005-1.

Cable gland entries:
Conduit installation needs to be UL/ cUL listed fittings suitable for knockout openings. The supply wiring has to be enclosed in metal
conduits for products for Fire Alarm Use.
According to CSA-C22.2 No. 205-M1983 clause 4.3.4 the connection is limited to max. three leads.

Installation:
The units shall be installed indoors or outdoors in accordance with the manufacturer’s installation instructions as well as the National
Electrical Code (NFPA 70) and the National Fire Alarm Code (NFPA 72) for the units evaluated for Public Fire Alarm applications in the
U.S. In Canada, they shall be installed in accordance with the Canadian Electrical Code, Part 1 and the Standard for the Installation of
Fire Alarm Systems CAN/ULC-S524-M91 for the units evaluated for Public Fire Alarm applications. The installation shall also be in a
manner acceptable with the local authority having jurisdiction.

For audible application for Fire Alarm Service use both terminals for connection. Break wire run to provide Electrical Supervision (see
UL 464 clause 39.1e). The tone no. 111 is to be used for evacuation use only
(see UL 464 clause 39.1e)

cUL directional characteristics for
the horn:

AXIS

ANGLE

dBA

Horizontal

32 deg. left or right

-3

Horizontal

28 deg. left or right

-6

Vertical

32 deg. left or right

-3

Vertical

28 deg. left or right

-6

Min. Output sound pressure
level: [dB(A)]

Type

Voltage

UL 464 db(A) at 10 ft ++

CAN/ULc-S525-07

PA 1-24 DC

18V DC

77,1 (for tone 113)

86,2 (for tone 60)

Tone no. 2, 15, 60, 104, 131, 146, 111, 112, and 113 was used for this test.


Connecting cables:

7 [0.28"]

7 [0.28"]

solid

stranded

This manual is related to the following products: