A MAJOR CAUSE OF VENT

RELATED FIRES IS FAILURE

TO MAINTAIN REQUIRED

CLEARANCES (AIR

SPACES) TO COMBUSTIBLE

MATERIALS. IT IS OF THE

UTMOST IMPORTANCE THAT

DURABLACK BE INSTALLED

ONLY IN ACCORDANCE WITH

THESE INSTRUCTIONS.

NOTE:

Read through all of these instructions

before beginning your installation. Failure

to install as described in this instruction

will void the manufacturer’s warranty, and

may have an effect on your homeowner’s

insurance. Keep these instructions for

future reference.

NOT A UL LISTED PRODUCT

Dear Customer, Installer, or End User:

We welcome any comments, ideas, input or

complaints regarding DuraVent products.

If you are searching for tech support or product

information, please phone us at 800-835-4429.

Or email us at:

[email protected]

IMPORTANT

DuraBlack must be installed with at least an

18” Clearance to Combustibles.

Read all instructions carefully before starting

the installation. The DuraVent warranty will be

voided, and serious fire, health, or other safety

hazards may result from any of the following

actions:

• Installation of any damaged DuraBlack

component.

• Unauthorized modification of any

DuraBlack component

• Installation of any component part not

manufactured or approved by DuraVent.

• Installation other than as instructed

by DuraVent and the appliance

manufacturer. Consult your local building

codes before beginning the installation.

INSTALLATION PROCEDURE

Prior to beginning your installation, please

verify what style connector pipe you have. You

may have "Locking Tab" style, or "Trim Ring"

style per Fig.1. These are the methods for

attaching your connector pipe to the support

box (Fig.2).

Step 1. Insert the adapter or Connector

section of pipe into the previously installed

Ceiling Support Box. Position it so the seams

are facing the wall, and the smooth side is

facing the room. For "Locking Tab" connectors,

push the pipe in firmly, until the locking notches

engage the top of the rim of the hole in the

support box. For "Trim Collar" style connector,

insert the pipe into the support box. Slide the

trim collar on and slide up to the support box,

until it is next to the pipe bead. Using the four

pre-punched holes in the trim collar as a guide,

drill 1/8" diameter holes in the support box, and

affix using the sheet metal screws provided. It

is extremely important that the Support Box

be positioned so that the single wall pipe is

at least 18” from the combustible wall, and

also that the support box protrudes at least

2” below the ceiling.

Reposition the Support Box if necessary, to

meet these two requirements.

Step 2. If you have "Locking Tab" style

connectors and you are installing the optional

Trim Collar, slide the Trim Collar upwards over