10

enclose the attic portion of the chimney in

a framed enclosure (always maintain 2”

air-space clearance to combustibles). If the

chimney is fully enclosed through the attic, an

Attic Insulation Shield is not required. Install

the Attic Insulation Shield as follows:

a. Remove any insulation or debris from attic

floor around the framed opening.

b. Assemble Chimney Sections until at least 18

inches of chimney extends above the Firestop.

c. Slip the Attic Insulation Shield over the

Chimney until the base sits squarely on the

framed opening (Fig. 9).

d. Secure the Attic Insulation Shield to the

top of the framed opening using at least (2)

8-penny nails or (2) #8, 1-1/2” wood screws

per side (Fig. 10).

e. Wrap the Collar of the Attic Insulation

Shield around the chimney and fasten it

loosely. Slide the Collar down to meet the Attic

Insulation Shield. Tighten the bolts to secure

the Collar in place (Fig. 10).

11. Install Roof Radiation Shields: Roof

Radiation Shields provide protection for roof

or chase framing members. Note: Roof

Radiation Shields do not allow for a reduced

clearance to combustibles. Clearance

to combustibles must be a minimum of 2"

away from the chimney pipe. Install Roof

Radiation Shields at either the top of the

chase or where the chimney penetrates the

roof, whichever is the top of the installation.

Roof Radiation Shields are built with a 1/2" air

gap standoff from the joist face (Fig. 11). The

corners of the Roof Radiation Shields overlap

each other to ensure proper position. Secure

the Roof Radiation Shields to the top of the

framing members using screws or nails in the

corners (Fig. 11). If framing members are further

away from the chimney than 2", center the Roof

Radiation Shield to the chimney on the framing

Figure 13

1 1/2” VENTILATION OPENING

AROUND CHIMNEY PIPE

MINIMUM

1/2 INCH

AIR SPACE

1/2 INCH

ESTABLISHED

BY SPACERS

AIR SPACE

1/2"

CHASE TOP

FLASHING

REQUIRED

SPACERS

Figure 12

Figure 11

(4) ROOF

RADIATION

SHIELDS

CHASE

ENCLOSURE