• Use of a collar when connecting to the return duct is

recommended.

• 6" round galvanized ductwork is recommended.

• Be sure to install two balancing dampers, see Figure

11, page 16.

EXHAUST AND FRESH AIR OUTDOOR CONNECTIONS

(Stale Air To Outdoors and Fresh Air From Outdoors)

• Insulated duct (often flexible ducting) of at least R-4

insulating value with a continuous vapor barrier must
be used for both duct runs connecting the Energy
Recovery Ventilator to the outdoors. The vapor barrier
must be sealed at both ends and extend from the
Aprilaire Energy Recovery Ventilator Housing to the
header (outer wall).

NOTE:

In some areas, local codes prohibit a direct

connection to the forced air system. In this case an
“INDIRECT” or “SOFT” CONNECTION must
be made.

• The fresh air intake hood and exhaust air outlet hood

must be located at least 10' apart to avoid cross contami-
nation. Also, the fresh air intake should be a minimum of
10 feet from an appliance vent that exhausts toxic
gases.
Using adjacent walls around an outside corner
will accomplish this easily. Both of these hoods should
be at least 18" above the ground or above the expected
snow line, whichever dimension is greater.

• The duct runs should be kept as straight, short and

equal as possible to minimize resistance and optimize
blower performance. Also, try to use as few bends and
restrictions as possible.

DO NOT connect the exhaust outlet into an attic, storage

or garage space. This can cause excess moisture to
collect in these areas, causing possible damage to the
home from outdoors.

• The fresh air intake must be mounted in a location

removed from sources of pollution and extreme temper-
atures such as furnace exhaust, car exhaust, dryer
vents, central air condensing units, pet enclosures, etc.

DO NOT connect the Aprilaire Energy Recovery

Ventilator exhaust to any gas appliance flue.

• Both intake and exhaust hoods must have a screen to

prevent small animals, insects, and large airborne
debris from entering the ductwork. This screen must be
accessible for easy cleaning. Both hoods must be
caulked to prevent water leakage.

WARNING:

120 Volts may cause serious injury from

electrical shock. Leave unit disconnected until
installation is complete.

G. ELECTRICAL CONNECTION

• The power cord can be plugged into any 120 VAC

grounded outlet preferably within 30" of unit.

• It is recommended that Aprilaire

®

Energy Recovery

Ventilator ductwork remains separate from bathroom
exhaust fan ducts.

• Galvanized ductwork (6" round) is recommended

between the living space return grille and return inlet.
If rectangular duct is used, be sure it has an equivalent
air flow rating. Undersized ducting can cause air flows
to be out of balance or air flow reductions in the system,
resulting in poor performance.

• With any blower system, some sound is transferred

along the ductwork. A sound absorber at least 6' long
consisting of 1" thick rigid fiberglass duct or insulated
flexible duct (ATCO series 70 or equivalent) is recom-
mended for maximum absorbing of air movement sounds
between the unit and the living space return grille. A
balancing damper must be installed in this duct near the
Aprilaire

®

Energy Recovery Ventilator, see Figure 11,

page 16. Install an air flow measuring device at least 5'
from damper in straight section and then complete the
system installation before proceeding to the balancing
instructions found on page 15.

SUPPLY: Fresh Air From Unit to House

(Fresh Air To House)

• The supply duct should be connected directly to the

forced air system return duct a minimum of 10' from the
furnace blower. Avoid making this connection in the
area of any return grille.

FRESH AIR TO HOUSE

SUPPLY AIR

RETURN AIR

FURNACE

FRESH AIR FROM OUTSIDE

STALE AIR TO OUTSIDE

AIR MOVEMENT SOUND ABSORBER

FIGURE 1

FRESH

AIR TO

HOUSE

INSTR.

LABEL

ENERGYMAX

®

TRANSFER CORE

E Z KLEEN

®

WASHABLE ALUMINUM

AIR FILTERS

POWER

CORD 120

VAC

STALE AIR

FROM

HOUSE

FRESH AIR

FROM

OUTSIDE

STALE AIR

TO OUTSIDE
(INSULATED

DUCT)

(DAMPERED

DUCT)

BLOWER

ASSEMBLY

(INSULATED

DUCT)

(DAMPERED

DUCT)

STALE AIR FROM HOUSE

(Centrally Located such as

Hallway or Foyer)

Note: In climates where the outdoor temperature

drops below 10°F (-12°C), the fresh air inlet duct
insulation must extend all the way to the Aprilaire
Energy Recovery Ventilator housing. Extra
insulation may be needed at the fresh air inlet
duct connection to the unit.