Performance data — ht 060 - full load, Htv/htd/hth series, Installation, operation & maintenance – Comfort-Aire HTH Series User Manual
Page 40: Heat controller, inc

40
Installation, Operation & Maintenance
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Performance Data — HT 060 - Full Load
1825 CFM Nominal (ISO Rated) Airfl ow Cooling, 2050 CFM Nominal (ISO Rated) Airfl ow Heating
Performance capacities shown in thousands of Btuh
EWT
°F
Cooling - EAT 80/67°F
Heating - EAT 70°F
GPM
WPD
CFM
TC
SC
kW
EER
HR
LWT
HWC
GPM
WPD
CFM
HC
kW
COP
HE
LAT
LWT
HWC
PSI
FT
PSI
FT
20
Operation not recommended
15.0
7.3
16.8
1750
42.8
3.89
3.2
29.5
92.6
16.1
4.0
15.0
7.3
16.8
2050
43.4
3.77
3.4
30.6
89.6
4.1
3.8
30
7.5
1.7
3.9
1590
75.3 49.7
2.68
28.1
84.4
22.9
1.9
7.5
1.7
3.9
1750
46.9
3.95
3.5
33.4
94.8
21.1
4.1
7.5
1.7
3.9
1850
76.6 53.4
2.78
27.5
86.1
22.9
2.0
7.5
1.7
3.9
2050
47.6
3.82
3.6
34.5
91.5
9.2
4.0
11.3
3.7
8.6
1590
74.9 50.3
2.57
29.1
83.6
15.2
1.8
11.3
3.7
8.6
1750
49.1
3.98
3.6
35.6
96.0
23.7
4.2
11.3
3.7
8.6
1850
76.2 54.0
2.67
28.5
85.3
15.2
1.8
11.3
3.7
8.6
2050
49.9
3.86
3.8
36.7
92.5
6.5
4.1
15.0
6.1
14.1
1590
74.2 50.5
2.53
29.3
82.9
11.3
1.8
15.0
6.1
14.1
1750
50.4
4.00
3.7
36.7
96.7
25.1
4.2
15.0
6.1
14.1
1850
75.5 54.3
2.62
28.8
84.5
11.3
1.8
15.0
6.1
14.1
2050
51.2
3.88
3.9
37.9
93.1
5.1
4.1
40
7.5
1.2
2.7
1590
74.4 48.8
2.86
26.0
84.2
22.9
2.3
7.5
1.2
2.7
1750
53.9
4.06
3.9
40.0
98.5
29.3
4.4
7.5
1.2
2.7
1850
75.7 52.5
2.97
25.5
85.8
22.9
2.3
7.5
1.2
2.7
2050
54.7
3.94
4.1
41.3
94.7
11.0
4.2
11.3
3.0
7.0
1590
75.2 49.5
2.72
27.6
84.5
15.3
2.0
11.3
3.0
7.0
1750
56.7
4.12
4.0
42.7
100.0
32.4
4.5
11.3
3.0
7.0
1850
76.5 53.2
2.82
27.1
86.1
15.3
2.0
11.3
3.0
7.0
2050
57.6
3.99
4.2
44.0
96.0
7.8
4.4
15.0
5.3
12.2
1590
75.3 49.8
2.66
28.3
84.3
11.5
1.9
15.0
5.3
12.2
1750
58.3
4.15
4.1
44.1
100.8
34.1
4.6
15.0
5.3
12.2
1850
76.6 53.6
2.76
27.8
86.0
11.5
1.9
15.0
5.3
12.2
2050
59.2
4.02
4.3
45.5
96.7
6.1
4.4
50
7.5
0.9
2.0
1590
72.4 47.8
3.08
23.5
82.9
22.5
2.8
7.5
0.9
2.0
1750
61.1
4.21
4.3
46.8
102.4
37.5
4.7
7.5
0.9
2.0
1850
73.6 51.4
3.20
23.0
84.5
22.5
2.9
7.5
0.9
2.0
2050
62.1
4.08
4.5
48.2
98.0
12.8
4.6
11.3
2.6
6.0
1590
74.0 48.6
2.91
25.4
84.0
15.2
2.4
11.3
2.6
6.0
1750
64.5
4.28
4.4
49.9
104.1
41.1
4.9
11.3
2.6
6.0
1850
75.3 52.2
3.02
25.0
85.6
15.2
2.5
11.3
2.6
6.0
2050
65.5
4.15
4.6
51.3
99.6
9.1
4.7
15.0
4.7
10.8
1590
74.6 48.9
2.83
26.3
84.3
11.5
2.2
15.0
4.7
10.8
1750
66.3
4.32
4.5
51.6
105.1
43.1
5.0
15.0
4.7
10.8
1850
75.9 52.6
2.94
25.9
85.9
11.5
2.3
15.0
4.7
10.8
2050
67.3
4.19
4.7
53.0
100.4
7.1
4.8
60
7.5
0.7
1.7
1590
69.5 46.7
3.35
20.7
81.0
22.0
3.5
7.5
0.7
1.7
1750
68.5
4.37
4.6
53.6
106.2
45.7
5.1
7.5
0.7
1.7
1850
70.7 50.3
3.47
20.4
82.6
22.0
3.6
7.5
0.7
1.7
2050
69.5
4.24
4.8
55.1
101.4
14.7
5.0
11.3
2.4
5.4
1590
71.7 47.6
3.15
22.8
82.5
15.0
3.0
11.3
2.4
5.4
1750
72.3
4.46
4.7
57.1
108.3
49.9
5.3
11.3
2.4
5.4
1850
73.0 51.1
3.26
22.4
84.1
15.0
3.1
11.3
2.4
5.4
2050
73.4
4.33
5.0
58.6
103.2
10.4
5.2
15.0
4.3
10.0
1590
72.7 48.0
3.05
23.8
83.1
11.3
2.8
15.0
4.3
10.0
1750
74.4
4.52
4.8
59.0
109.4
52.1
5.5
15.0
4.3
10.0
1850
74.0 51.6
3.16
23.4
84.8
11.3
2.8
15.0
4.3
10.0
2050
75.5
4.38
5.1
60.6
104.1
8.1
5.3
70
7.5
0.7
1.7
1590
66.1 45.5
3.67
18.0
78.7
21.4
4.4
7.5
0.7
1.7
1750
75.8
4.55
4.9
60.3
110.1
53.9
5.6
7.5
0.7
1.7
1850
67.3 48.9
3.81
17.7
80.3
21.4
4.5
7.5
0.7
1.7
2050
77.0
4.41
5.1
61.9
104.8
16.5
5.4
11.3
2.3
5.2
1590
68.6 46.4
3.43
20.0
80.4
14.6
3.8
11.3
2.3
5.2
1750
80.1
4.67
5.0
64.2
112.4
58.6
5.8
11.3
2.3
5.2
1850
69.8 49.9
3.56
19.6
82.0
14.6
3.8
11.3
2.3
5.2
2050
81.3
4.52
5.3
65.9
106.7
11.7
5.7
15.0
4.1
9.5
1590
69.9 46.9
3.32
21.0
81.2
11.0
3.5
15.0
4.1
9.5
1750
82.4
4.73
5.1
66.3
113.6
61.2
6.0
15.0
4.1
9.5
1850
71.1 50.4
3.44
20.6
82.8
11.0
3.5
15.0
4.1
9.5
2050
83.7
4.59
5.3
68.0
107.8
9.1
5.8
80
7.5
0.8
1.8
1590
62.5 44.1
4.05
15.4
76.3
20.8
5.5
7.5
0.8
1.8
1750
83.1
4.75
5.1
66.9
114.0
62.2
6.1
7.5
0.8
1.8
1850
63.5 47.5
4.19
15.1
77.8
20.8
5.6
7.5
0.8
1.8
2050
84.4
4.61
5.4
68.7
108.1
18.3
5.9
11.3
2.2
5.2
1590
65.1 45.1
3.78
17.2
78.0
14.1
4.7
11.3
2.2
5.2
1750
87.8
4.89
5.3
71.1
116.4
67.4
6.4
11.3
2.2
5.2
1850
66.2 48.5
3.91
16.9
79.6
14.1
4.8
11.3
2.2
5.2
2050
89.1
4.74
5.5
73.0
110.3
13.0
6.2
15.0
4.1
9.4
1590
66.4 45.6
3.65
18.2
78.8
10.7
4.3
15.0
4.1
9.4
1750
90.3
4.97
5.3
73.4
117.8
70.2
6.6
15.0
4.1
9.4
1850
67.5 49.0
3.78
17.9
80.4
10.7
4.4
15.0
4.1
9.4
2050
91.7
4.81
5.6
75.3
111.4
10.0
6.4
90
7.5
0.8
2.0
1590
58.7 42.6
4.49
13.1
74.0
20.2
6.7
7.5
0.8
2.0
1750
90.3
4.97
5.3
73.3
117.8
70.4
6.6
7.5
0.8
2.0
1850
62.3 47.0
4.33
14.4
77.1
20.2
5.9
7.5
0.8
2.0
2050
91.7
4.81
5.6
75.2
111.4
20.1
6.4
11.3
2.3
5.2
1590
61.3 43.7
4.18
14.7
75.5
13.7
5.8
11.3
2.3
5.2
1750
95.2
5.12
5.4
77.8
120.4
76.2
7.1
11.3
2.3
5.2
1850
62.3 47.0
4.33
14.4
77.1
13.7
5.9
11.3
2.3
5.2
2050
96.7
4.96
5.7
79.7
113.7
14.2
6.9
15.0
4.0
9.3
1590
62.6 44.2
4.03
15.5
76.4
10.4
5.4
15.0
4.0
9.3
1750
97.9
5.21
5.5
80.1
121.8
79.3
7.3
15.0
4.0
9.3
1850
63.7 47.5
4.18
15.2
77.9
10.4
5.5
15.0
4.0
9.3
2050
99.4
5.05
5.8
82.1
114.9
11.0
7.1
100
7.5
0.9
2.0
1590
55.2 41.1
5.00
11.0
72.3
19.7
8.1
Operation not recommended
7.5
0.9
2.0
1850
56.2 44.2
5.18
10.8
73.9
19.7
8.3
11.3
2.3
5.2
1590
57.5 42.1
4.65
12.4
73.4
13.3
7.1
11.3
2.3
5.2
1850
58.5 45.3
4.82
12.1
75.0
13.3
7.3
15.0
4.0
9.3
1590
58.8 42.6
4.48
13.1
74.1
10.1
6.7
15.0
4.0
9.3
1850
59.8 45.9
4.65
12.9
75.6
10.1
6.8
110
7.5
0.8
1.8
1590
52.2 39.6
5.60
9.3
71.3
19.4
9.8
7.5
0.8
1.8
1850
53.1 42.6
5.80
9.2
72.9
19.4
10.0
11.3
2.2
5.1
1590
54.1 40.6
5.20
10.4
71.8
13.1
8.7
11.3
2.2
5.1
1850
55.0 43.6
5.39
10.2
73.4
13.1
8.8
15.0
4.0
9.2
1590
55.2 41.1
5.01
11.0
72.3
9.8
8.2
15.0
4.0
9.2
1850
56.1 44.2
5.19
10.8
73.8
9.8
8.3
120
7.5
0.6
1.3
1590
50.0 38.5
6.30
7.9
71.5
19.5
11.7
7.5
0.6
1.3
1850
50.8 41.4
6.53
7.8
73.1
19.5
11.9
11.3
2.0
4.7
1590
51.3 39.2
5.83
8.8
71.2
12.9
10.4
11.3
2.0
4.7
1850
52.2 42.1
6.04
8.6
72.8
12.9
10.6
15.0
3.8
8.8
1590
52.1 39.6
5.62
9.3
71.3
9.7
9.8
15.0
3.8
8.8
1850
53.0 42.6
5.82
9.1
72.9
9.7
10.0
Interpolation is permissible; extrapolation is not. Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. See performance correction tables for operating conditions other than those listed above.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. For operation in the shaded areas, please see the Performance Data Selection Notes.
All performance is based upon the lower voltage of dual voltage rated units.