The RDM-2DC Dual DC Module (FG606-61) is a 1920 W module used for the
dimming of fluorescent ballast loads. It uses a 0 to 10 VDC current sinking for
use with four-wire ballasts. It is designed for use with the RDA series of
enclosures, in an AMX Lighting™ modular digital dimming system. The module’s
120 and 277 VAC ratings are CE, UL, and C-UL approved.

RDM-2DC UL and C-UL Ratings

120 VAC, 50/60 Hz, 1920 W

277 VAC, 50/60 Hz, 1920 W

Control Out: 50 mA, 12 VDC sinking

Suggested Dimmed Loads

Four-wire dimmable ballasts, like Advance Transformer Mark VII™ or the

Energy Savings SuperDim™ series

Specifications

Dimensions (HW): 10" x 2.75" (25.4 cm x 6.99 cm)

Non-phase dependant

Use wires rated at 75°C (167°F)

Torque terminals to 20 in-lbs. (2.3 N/M)

Max. wire size: 10 AWG (4 mm²)

Wire stripping length: 0.28" (7 mm)

Weight: 2.6 lbs. (1.180 kg)

BTU/hr: 150

Control current: 125 mA @ 12 VDC per control port

Caution: Pre-Installation Notes

All Class 1 wiring must be connected to proper terminals.

All control wiring must be connected to proper terminals.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times.

Use low-voltage wires with a 300 volt rating or greater.

Use field installed copper conductors.

All electrical ratings are for continuous duty.

For indoor use only.

Test loads for shorts before connecting.

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-2DC to the AMX Lighting Master

Lighting Application Drawings

Warning: Failure to ground the ballast may cause ballast failure

FIG. 1 RDM-2DC

Low-voltage control
wiring: 4-pin

Relay

+ out (LV)

- out (LV)

Line in

Load out

High

Low-voltage

voltage

connector to AMX
Lighting master
controller

Mounting
points

+ out (LV)

- out (LV)

Line in

Load

High

Low

voltage

Relay

voltage

Fuses

out

FIG. 2 Connecting the RDM-2DC and AMX Lighting Master

FIG. 3 RDM-2DC application wiring

Pin 4 (GND)

Pin 3 (RLY)
Pin 2 (DIM)

Pin 1 (+12 V)

RDM-2DC 4-pin module connector

1 (+)

2 (DIM)

3 (-)

GND

4-pin plug from RDM series module

Note: The 4-pin plugs from the module connector to the 4-pin
connector on the master (black plug cover facing up).

Ballast

Florescent

Neutral

Line in (HOT)

Load

Neutral

+

-

Circuit breaker
panel

Ballast

The fuses protect the dimming
circuit from a low impedance load.

The fuse will blow if it were

incorrectly wired

Catastrophic ballast failure

Reversing switched and

dimmed circuits

Reversing dimmed and

line circuits.

The dimmed output must be
connected to a high impedance
load.