SV9560/SV9570 SMARTVALVE

®

WATER HEATER CONTROL

TROUBLESHOOTING GUIDE

START

l

CHECK FOR PROPER VOLTAGE AT
CONTROL HARNESS (SEE INSET A).
VOLTAGE SHOULD BE 120V
BETWEEN 120V COMMON AND
120V HOT.

TURN ON GAS SUPPLY PLUG
HARNESS INTO SmartValve

®

CONTROL. INITIATE A REQUEST
FOR HEAT. COMBUSTION BLOWER
SHOULD BE ON AND PREPURGED.

IGNITER WARMS UP AND
GLOWS RED.

MAIN VALVE OPENS AND MAIN
BURNER LIGHTS.

SYSTEM IS OKAY.

CHECK:
• LINE VOLTAGE POWER
• WIRING

WARNING

Line Voltage Hazard.
Can cause property damage,
severe injury or death.

Only a trained, experienced service
technician should perform this trouble-
shooting. Be certain to avoid contact
with pressure switch and/or electrical
connections.

CHECK:
• IS AIR PROOFING SWITCH STUCK

OR CLOSED.

• IS THE FLUE BLOCKED.
• IS THE WIRING CONNECTED

PROPERLY TO THE SWITCH AND
COMBUSTION BLOWER.

WITH IGNITER CABLE CONNECTED,
MEASURE VOLTAGE AT HSI ELEMENT
OUTPUT (SEE INSET B) 120V NOMINAL
CHECK DAMAGED OR BROKEN HSI
ELEMENT.

WARNING

Line Voltage Hazard.
Can cause property damage,
severe injury or death.

Only a trained, experienced service
technician should perform this trouble-
shooting. Be certain to avoid contact
with pressure switch and/or electrical
connections.

REPLACE HSI

CHECK:
• IS THE APPLIANCE EARTH GROUNDED

(120V BETWEEN HOT AND CHASSIS
GROUND).

• IS GAS SUPPLY OFF OR TOO LOW

PRESSURE TO OPERATE THE
CONTROL.

• DOES BURNER FLAME MAKE GOOD

CONTACT WITH THE FLAME ROD.

• IS FLAME SENSE ROD CONTAMINATED

OR IN AN INCORRECT LOCATION.

• IS THERE APPROXIMATELY 100 VAV

BETWEEN FLAME ROD AND BURNER
PAN WITH 120VAC INPUT TO
CONTROL.

• IF ALL OF THE ABOVE ARE GOOD,

REPLACE IGNITER AND FLAME ROD
ASSEMBLY.

CYCLE THERMOSTAT OFF AND BACK ON

MAIN BURNER LIGHTS

REPLACE SmartValve

®

CONTROL

NOTE: BEFORE TROUBLESHOOTING
BECOME FAMILIAR WITH THE STARTUP
AND CHECKOUT PROCEDURE.

REPLACE SmartValve

®

CONTROL

WHEN MEASURING VOLTAGE
AT CONNECTIONS, USE CARE
TO ASSURE TERMINALS ARE
NOT DAMAGED.

1

1

1

NO

NO

NO

NO

NO

YES

YES

NO