On power, True on line sinewave double conversion ups, Technical features – Atlantis Land A03-OP6000 User Manual
Page 2

A
TLANTIS
L
AND
S.p.A. - Viale De Gasperi 122 - 20017 Mazzo di Rho - Milano - ITALY
Phone: +39 - (0)2 - 93.90.60.85 Fax: +39 - (0)2 - 93.90.61.61 - Web: www.atlantis-land.com - E-Mail: [email protected]
Subject to change without notice
True On Line Sinewave
Double Conversion UPS
A0
3-
OP
60
00
_S
E_
06
3
TECHNICAL FEATURES
MODEL
A03-OP6000
Power Rating
6000 VA - 4200 W
INPUT
Voltage (Vac)
160-280
Frequency (Hz)
50 ± 5% (Auto Sensing)
Phase
SingleLine+Neutral+Ground
Input Power Factor
> 0.99 (Full Load)
OUTPUT
Voltage (Vac)
220/230/240
Voltage Regulation
± 2%
Voltage Adjustement
± 0%; ± 1%; ± 2%; ± 3%
Frequency Stability
±0.2% (Free Running)
Frequency Regulation
± 1%; ± 3%
Wave Form
Sine Wave, THD<4%
(no load to full load)
Rated Power Factor
0.7
Transfer Time
0 ms
Crest Factor
3:1
Efficiency (AC to AC)
>90% (Normal)
Efficiency
(AC to AC, ECO)
>98% (ECO)
Run Time (Full Load)
> 8 min
DC Start
Yes
BATTERY
Type
Maintenance Free Sealed
Lead Acid
Quantity (pcs)
20
Voltage (Vdc)
240
Recharge Time
4 Hours to 90%
Supplem. Charger
Optional 1000W Isolated
chargers
PROTECTION
Short Circuit
Hold Whole System
OverHeat
Switch to Bypass
High Voltage Trip
Switch to Backup Mode
Battery Low
Alarm and Switch Off
Noise Suppression
Complies with EN50091-2
Spike Suppression
Complies with EN610000-4-5
OverLoad
AC Mode:
1) <105% continuously Alarm
2) 105%-150% delay 40
seconds before switching to bypass
4) >150% immediately
switching to bypass
Backup Mode: Same Delay
Time as AC Mode, then
completely shutdown
MODEL
A03-OP6000
ALARMS
Audible and Visual
Line Failure, Battery Low, Tranfer to Bypass,
System Fault Conditions
DISPLAY
Self Diagnostics
Push Button (On Demand)
LED+LCD
Utility, Battery, Inverter, Bypass, Self-Test,
OverLoad, Load/Battery Level and Fault
PHYSICAL
Dim (WxDxH)
290 x 645 x 748 mm
Outlets
Terminal Block
Net Weights (Kgs)
80
ENVIRONMENTAL
Operating
Temperature
0-40
o
C
Temperature Warning
The battery design life is based on a
temperature of 25
o
°C. Ambient temperature
above this range will reduce battery life
Altitude / Humidity
0-2000m up to 40°C, 3000m up to 35°C /
90% RH Humidity max (non-condensing)
Noise
< 45 dB (at 1 metere)
COMPUTER
INTERFACE
Interface Type
Standard RS232 Interface / SNMP
Protocol
MEGATEC Protocol
AS 400 Interface
Optional As400/ Basic Photo Contact
Interface Board provides Utility Failure,
Battery Low, Bypass Active, UPS
Shutdown functions
SNMP Adaptability
Slot for Standard SNMP Card
Compatibility of
Bundled Software
UPSilon2000 for: Novell NetWare,
Windows95/98, Windows NT, Windows ME,
Windows 2000 and XP, Linux and FREE BSD
Optional Software
UPSilion for UNIX, SNMP Adapter, USBMate
SAFETY
CONFORMANCE
Quality Assurance
ISO9001 Certified Company
Marks
CE
On Power