INSTALLATION

The success of a DC to AC power inverter installation depends mainly on the methods and
materials used for installation. Please read and comply with instructions given below

GENERAL
Installation and wiring compliance
- Installation and wiring must comply with the local and the national electrical codes and

must be done by a certified electrician

- In building / residential applications, electrical codes do not allow permanent connection

of AC distribution wiring to the inverter’s AC output receptacles. The receptacles are
intended for temporary (as needed) connection of cord connected loads only. (Model
PSE-12275A has a provision for hard wiring to an electrical breaker panel / load center.
Read details under “AC Power Distribution and Grounding” on page 8.

- The inverter does not have integral over current protection for the AC output side ( Except

in the case of model PSE-12275A where a 15 A breaker is provided if the AC output is to
be fed directly from the front panel of the unit through the NEMA 5-15R receptacle ).
Protection should be provided by the installer

- Over current protection of the cables from the battery to the inverter has to be provided by

the installer

- The DC input positive and negative terminals are isolated from the chassis. Similarly, the

neutral pole of the AC receptacles / the neutral wire is not bonded to the chassis. System
grounding to suit the national / local electrical codes is to be undertaken by the installer.
Read details under “AC Power Distribution and Grounding”on page 8.

Preventing electrical shock
- Always connect the grounding connection on the inverter to the appropriate grounding

system. Read details under “AC Power Distribution and Grounding” on page 8.

Installation environment
- The inverter should be installed indoor only in a well ventilated, cool, dry environment
- Do not expose to moisture, rain, snow or liquids of any type.
- To reduce the risk of overheating and fire, do not obstruct the suction and discharge

openings of the cooling fan.

- To ensure proper ventilation, do not install in a low clearance compartment
- Working with the inverter may produce arcs or sparks. Thus, the inverter should not be

used in areas where there are inflammable materials or gases requiring ignition protected
equipment. These areas may include spaces containing gasoline powered machinery, fuel
tanks, battery compartments

Mounting position of the inverter
-
The inverter may be mounted horizontally on the top of a horizontal surface or under a

horizontal surface. The inverter may be mounted on a vertical surface only horizontally
(the fan axis should always be horizontal i.e. the fan should not be pointing up or
down)