20 | SAMLEX AMERICA INC.

SAMLEX AMERICA INC. | 21

cAteGoRY

PARAMeteR

SPeciFicAtion

AC INPUT

Input Voltage

230 VAC Nominal (+6% / -10%), 50/60 Hz

Input Current

2.75A @ 120 VAC

Input Current at No Load

105 mA ± 10%

Inrush current at Startup

32A ±5% for 2.4 ms

DC oUTPUT

Output Voltage at Load Terminals

13.8VDC ± 0.1V

Output Voltage at Battery

Terminals (Without battery)

13.8VDC ± 0.1V

Output Voltage at Battery

Terminals (With battery)

Actual battery voltage corresponding to

State of Charge; 13.5V ± 0.2V when battery is

fully charged and floating

Output Voltage Noise and Ripple

< 150 mV Peak to Peak

Continuous Output Current at

Load Terminals

19A (With battery backup);

23A (Without battery backup)

Continuous Output Current at

Battery Terminals (Battery Backup)

Up to 4A (When battery is completely discharged

to Standing Voltage of 11.4V)

Output Current Limit at Load

Terminals

- 25A for 100 sec (External 25A fuse will blow)

- Surge > 25A as permitted by Time Current

Characteristics of 25A load side fuse (In Battery

backup Mode)

Output Current Limit at Battery

Terminals (Battery Backup)

4A (When battery is completely discharged to

Standing Voltage of 11.4V)

Peak Efficiency

85% ± 5%

ExTErNAL

BACKUP BATTErY

Type & Voltage

Lead Acid, 12V

Capacity

40Ah to 100 Ah

ProTECTIoNS

Short Circuit, Overload

External 25A Fuse will blow

Over Voltage

Regulated by PWM Controller

Over Temperature

(Power Supply Section)

Output of Power Supply Section shuts down when

Power Transformer winding temperature ≥ 105°C

± 5°C / 221°F ± 9°F); Auto reset on cooling down

to ≤ 75°C ± 5°C / 167°F ± 9°F

CooLING Forced Air

Temperature controlled fan. ON when Power

Transformer winding temperature is ≥ 60°C ± 5°C

/ 140°F ± 9°F; OFF when cools down to ≤ 40°C ±

5°C / 104°F ± 9°F

fUSES

Internal AC Side Fuse

- 5 mm x 20 mm Glass Fuse

- 250V, 4A, Time Delay Type

- Bussmann: “GDC-4”; LittelFuse - “218004”

External Battery Side Fuse (By User) - 32V, 25 A, Fast Acting

- Within 7” of the Battery Positive Post

External Load Side Fuse (By User)

- 32V, 25 A, Fast Acting

- Within 7” from Load Terminal of the unit

SeCtIOn 9 |

Specifications