TROUBLESHOOTING - GENERAL

PROBLEM : Power ON/OFF switch does not illuminate when turned on.

PROBABLE CAUSE

SUGGESTED

REMEDY



No power in the AC outlet

Check there is power in the outlet.

AC side fuse inside the power

Replace the fuse inside the unit. See

supply is blown

fuse ratings at page 8

PROBLEM : AC side fuse blows as soon as power is turned on.

PROBABLE CAUSE

SUGGESTED

REMEDY



Unit is defective

Call technical support.


PROBLEM : The output voltage is 0 V or very low

PROBABLE CAUSE

SUGGESTED

REMEDY


Input voltage is very low

Check that the input voltage is 230 VAC


The unit is in current limit condition

Check the output terminals are not

due to overload caused by large reactive

shorted. Remove the load. If the output

loading or by the output being

voltage gets restored, the load is shorted

short circuited

or is offering large reactive impedance.



Unit is shut down due to over

Check that the fan has not failed or

temp. (SEC-1223CE)

the vent openings are not blocked

PROBLEM : Output voltage drops as soon as the load is switched on

PROBABLE CAUSE

SUGGESTED

REMEDY


The unit is going into current
limit protection mode








4.

Reduce the load current to less than
the current limit value. Motors,
pumps, compressors, relays, incan-
descent and halogen lamps and large
capacitors in the input section of the
DC devices draw very high inrush or
starting currents of up to 10 times
their normal operating currents. En-
sure that these inrush/starting cur-
rents are below the current limit value
of the power supply.