beautypg.com

Specifications – Clary S Series User Manual

Page 15

background image

T H E C O N T I N U O U S P O W E R C O M P A N Y

Page 15

SPECIFICATIONS

ELECTRICAL

Input

Voltage (Auto-selectable)

120VAC +10%, -20%
(without Battery discharge)

Power Factor Corrected

IAW MIL STD. 1399 Sec. 300

Frequency

45 to 65Hz

Current

See Model Selection Guide

Output

Voltage

120VAC

± 3%

Frequency

50Hz / 60Hz (software select)
Line Sync (software select)

Current

See Model Selection Guide

Crest Factor Ratio
(Non-linear load and
less than 5% THD) Typical

@50% Load Up to 4.8:1
@75% Load Up to 3.2:1
@100% Load Up to 2.4:1

Total Harmonic Distortion (THD)

3% Typ; 5% Max.
(@100% Non-linear load)

Dynamic Response

±4% for 100% Step Load
Change,
0.5 Millisecond Recovery Time

Overload

110% for 10 Minutes;
200% for 0.5 Seconds

Efficiency (UPS)

88% Typ.

Battery Back-up

See Model Selection Guide

UPS Protection

Input and Output Short Circuit;
Input and Output Overload;
Excessive Battery Discharge

ENVIRONMENTAL

Operating Temperature

32

o

F to 104

o

F (0

o

C to 40

o

C)

Humidity

0% to 95% Non-condensing

Altitude

Sea Level to 10,000 Feet

Audible Noise

39-42 dBA at Five Feet

MECHANICAL

Input Inlet (6’ Line Cord Provided)

1000-1500VA

2000VA

NEMA 5-15Plug
NEMA 5-20Plug

Output (Qty.)

(1) Duplex 5-15R

Cooling

Low Velocity, Temperature
Controlled Reversible Forced
Air

Dimensions

See Model Selection Guide

Weight

See Model Selection Guide

DESIGN

Standard Features

Power Factor Corrected, Digital

Regenerative

™ On-Line, Sinewave

Inverter Powers Load Continuously
Extended Brownout Protection
Designed for Non-linear Loads
Continuous Operation on

-20%,+12% Line

Automatic Bypass
RS232 Data Interface
Software Selectable Output

Frequency

AC Output Switch
Auxiliary Battery Connector
Optional SNMP Interface

Specifications UL

Design

FCC Class A
IEEE 587/ANSI C62.41

MTBF

In Excess of 100,000 Hours

Typical Recharge Time to
85% Capacity at 100% Load

8 Hours

CONTROLS AND INDICATORS

Visual Indicators

Sequenced LEDs

Single LED

Battery Level, Load Level

AC Input, Inverter On, Fault
Fault Silent, AC Output,
Cold Start, Replace Battery

Front Panel Controls

Power On, Cold Start
Fault Silence, Battery Test
AC Output On/Off

Audible Alarms

Utility Interrupt, Inverter Failure
Overload, Low Battery

RS232 Data Interface (DB-9F)

Full Interactive, Remote Computer
Monitoring and Control of UPS
Functions.

Compatible with Systems
Enhancement UPS Monitor &
Control Software

Open-Collector (DB-9F)

Allows Alarm Function Monitoring

Optional SNMP Interface

(RJ45)

Allows Full Control and Monitoring
Over Network Connection.

Specifications subject to change without notice.

7/99