beautypg.com

Care and maintenance – Clary CT Series User Manual

Page 16

background image

T H E C O N T I N U O U S P O W E R C O M P A N Y

Page 16

CARE AND MAINTENANCE

his device is designed to be maintenance-free.
It can be cleaned with a damp cloth or
nonabrasive cleanser.
WARNING: Do not use ACETONE-BASE

cleaning solutions. Keep cleaning solutions out of
the electrical receptacles on this device.
Be sure filters, vents and fans are kept free from
accumulation of dust, dirt or lint. Below is a simple
maintenance schedule that will assist you in keeping
the system at its peak level of performance and also
minimizing potential premature failures.
Your system contains sealed maintenance-free
batteries. When situated in the proper environment,
with the proper charging and limited cycling, these
batteries can last many years.
WARNING: Never attempt to service batteries. High
voltage exists within the unit which could cause
electrical shock. Servicing of batteries should be
performed or supervised by personnel
knowledgeable of batteries and the required
precautions. Keep unauthorized personnel away
from batteries. When replacing batteries, use the
same number and type batteries.
CAUTION - Do not dispose of battery or batteries in
a fire. The battery may explode.

CAUTION - Do not open or mutilate the battery or
batteries. Released electrolyte is harmful to the skin
and eyes. It may be toxic.
CAUTION - A battery can present a risk of electrical
shock and high short circuit current. The following
precautions should be observed when working on
batteries.
1. Remove watches, rings, or other metal
objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of batteries.
5. Disconnect the charging source prior to

connecting or disconnecting battery terminals.

6. Determine if the battery is inadvertently

grounded. If inadvertently grounded, remove
source of ground. Contact with any part of a
grounded battery can result in electrical shock.
The likelihood of such shock will be reduced if
such grounds are removed during installation and
maintenance.

The internal rechargeable battery is recyclable. At
the end of its useful life, under various state and local
laws, it may be illegal to dispose of this battery into
the municipal waste stream. Check with the factory
for details in your area for recycling options or proper
disposal.

RECOMMENDED PREVENTATIVE MAINTENANCE SCHEDULE

TIME TASK

TOOLS

REQ’D

INITIAL

;

Every 6 mo.

Test battery operation, check back-up time

None

Every 12 mo.

Thoroughly clean unit

Vacuum, brush

Every 42 mo.

Replace battery

Screwdriver

Every 72 mo.

Replace cooling fan

Screwdriver

T

!

CAUTION

RISK OF ELECTRIC

SHOCK DO NOT OPEN