LOCATION OF UNIT: The Model 8901RFK Hose Spray can be installed at any 1/2" 
NPT port, pressure side. (See installation drawing). Fittings supplied make kit 
adaptable to eye/face wash, shower, and combination models. In order to comply with 
state codes, the use of a vacuum breaker is required with all eye/face wash and body 
spray units (Haws offers Model SP212). 
 
 SUPPLY LINE: The minimum recommended line size is 1/2" IPS with 30-90 psi (2-6 
ATM) pressure. Where sediment or mineral content is a problem, an inlet filter is 
recommended. 
TROUBLESHOOTING
PROBLEM
REPAIR CHECKLIST
1.
No flow.
1. a. Check the main shut-off valve.
2.
Insufficient water flow.
2. a. Verify minimum 30 psi (2 ATM)
flowing supply line pressure.
b.
 
 
 
 
Probable clogging of flow control due 
to inadequate line flushing. 
Disassemble eyewash at inlet 
connection to gain access and clean 
rubber flow control. 
c. Unscrew eye/face wash head cap off
to gain access to the buffer and clean 
it. 
 
 
 