Haws 8123 User Manual
Page 2

07/10
Model 8123
Page 2 of 5
LOCATION OF UNIT: The Model 8123 Emergency Shower should be installed in
close proximity to potential accident areas. It should be clearly identified free from
obstructions and easy to access.
SUPPLY LINE: The minimum recommended line size is 1” IPS with 30-90 psi (2-6
ATM) flowing pressure. Where sediment or mineral content is a problem, an inlet filter
is recommended.
PLUMBING CONNECTIONS: Inlet supply is female 1” IPS.
TROUBLESHOOTING
PROBLEM
REPAIR CHECKLIST
1. No flow.
1.
Check the main shut-off valve.
2. Insufficient water flow.
2. a. Verify minimum 30 psi (2 ATM)
flowing supply line pressure.
b. Probable clogging of flow control
inside showerhead. Unscrew
showerhead off of elbow and clean
rubber flow control.
For more information about Haws products, see our website:
www.hawsco.com
© 2010 Haws® Corporation – All Rights Reserved
HAWS® and other trademarks used in these materials are the exclusive property of Haws Corporation.