Start Up Conditions

CONDENSATION

Whenever the water heater is filled with cold water, a cer-

tain amount of condensation will form while the burner is

on. A water heater may appear to be leaking when in fact

the water is condensing. This usually happens when:

a. When a new water heater is filled with cold water for

the first time.

b. When gas burns and water vapor is produced in water

heaters, particularly high efficiency models where flue

temperatures are lower.

c. When you use large amounts of hot water in a short

time and the refill water is very cold.

Moisture from the products of combustion condenses on

the cooler tank surfaces and form drops of water which

may fall onto the burner or other hot surfaces and produce

a “sizzling” or “frying” noise.

Because of the suddenness and amount of water, conden-

sation water may be diagnosed as a “tank leak”. After the

water in the tank warms up (about 1-2 hours), the condition

should disappear.

Do not assume the water heater is leaking until there has

been enough time for the water in the tank to warm up.

An undersized water heater will cause more condensation.

The water heater must be sized properly to meet the fami-

ly’s demands for hot water including dishwashers, wash-

ing machines and shower heads.

Excessive condensation may be noticed during the winter

and early spring months when incoming water tempera-

tures are at their lowest.

Good venting is essential for a gas fired water heater to

operate properly as well as to carry away products of com-

bustion and water vapor.

SMOKE/ODOR

It is not uncommon to experience a small amount of smoke

and odor during the initial start-up. This is due to burning

off of oil from metal parts, and will disappear in a short

while.

THERMAL EXPANSION

Water supply systems may, because of such events as high

line pressure, frequent cut-offs, the effects of water ham-

mer among others, have installed devices such as pressure

reducing valves, check valves, back flow preventers,

etc...to control these types of problems. When these

devices are not equipped with an internal by-pass, and no

other measures are taken, the devices cause the water sys-

tem to be closed. As water is heated, it expands (thermal

expansion) and closed systems do not allow for the expan-

sion of heated water.

The water within the water heater tank expands as it is

heated and increases the pressure of the water system. If

the relieving point of the water heaters temperature-pres-

sure relief valve is reached, the valve will relieve the excess

pressure. The temperature-pressure relief valve is not

intended for the constant relief of thermal expansion. This

is an unacceptable condition and must be corrected.

It is recommended that any devices installed which could

create a closed system have a by-pass and/or the system

have an expansion tank to relieve the pressure built by ther-

mal expansion in the water system. Expansion tanks are

available for ordering through local plumbing supply hous-

es. Contact the local water supplier and/or plumbing

inspector for assistance in controlling these situations.

STRANGE SOUNDS

Possible noises due to expansion and contraction of some

metal parts during periods of heat-up and cool-down do

not represent harmful or dangerous conditions.
Condensation causes sizzling and popping with the burn-

er area during heating and cooling periods and should be

considered normal. See “Condensation” in this section.

Operational Conditions

SMELLY WATER

In each water heater there is installed at least one anode

rod (see parts section) for corrosion protection of the tank.

Certain water conditions will cause a reaction between this

rod and the water. The most common complaint associat-

ed with the anode rod is one of a “rotten egg smell”. This

odor is derived from hydrogen sulfide gas dissolved in the

water. The smell is the result of four factors which must all

be present for the odor to develop:

a. a concentration of sulfate in the supply water.

b. little or no dissolved oxygen in the water.

c. a sulfate reducing bacteria within the water heater.

(This harmless bacteria is non-toxic to humans.)

d. an excess of active hydrogen in the tank. This is

caused by the corrosion protective action of the

anode.

Smelly water may be eliminated or reduced in some water

heater models by replacing the anode(s) with one of less

active material, and then chlorinating the water heater tank

and all hot water lines. Contact the local water heater sup-

plier for further information concerning an Anode

Replacement Kit #9000029 and this Chlorination

Treatment.