beautypg.com

Troubleshooting chart, Fvir safety system operational checklist – State GS6 50 UOCT User Manual

Page 28

background image

28

FVIR Safety System Operational Checklist

TROUBLESHOOTING CHART

4. Manifold component block properly installed.
5. No leaks at pilot and manifold connection.
6. Burner door screws securely tightened.

1. Burner door gasket properly sealed.
2. Viewport not damaged or cracked.
3. Flame-trap free of debris and undamaged.

PROBLEM

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

BURNER WILL NOT IGNITE

1. Pilot not lit

2. Thermostat set too low

3. No

gas

4. Dirt in the gas lines

5. Pilot line clogged

6. Main burner line clogged

7. Non-functioning

thermopile

8. Non-functioning

thermostat

9. Heater installed in a confined area

1. Light

pilot

2. Turn temp. dial to desired temperature

3. Check with gas utility company

4. Notify utility-install trap in gas line

5. Clean, locate source and correct

6. Clean, locate source and correct

7. Replace

thermopile

8. Replace

thermostat

9. Provide fresh air ventilation

SMELLY WATER

1. Sulfides in the water

1. Replace the anode with a special anode

BURNER FLAME YELLOW-

LAZY

1. Insufficient secondary air

2. Low gas pressure

3. Flue

clogged

4. Main burner line clogged

5. Heater installed in a confined area

6. Obstruction in main burner orifice

1. Provide ventilation to water heater

2. Check with gas utility company

3. Clean, locate source and correct

4. Clean, locate source and correct

5. Proper fresh air ventilation

6. Clean or replace orifice

PILOT WILL NOT LIGHT OR

REMAIN LIT

1. Non-functioning

igniter

2. Thermopile connection loose

3. Air in gas line

4. Proper Lighting Sequence not followed.

Gas Control / Temperature Knob was not

held in for sufficient time.

5. Low gas pressure

6. No

gas

7. Dirt in gas lines

8. Cold

drafts

1. Replace igniter pilot assembly

2. Seat connector firmly in socket

3. Bleed the air from the gas line

4. Do not attempt to relight if the red light is lit

and the pilot flame is not visible through the

view port. Wait until the red light is no longer

lit, then follow lighting instructions on the water

heater.

5. Check with gas utility company

6. Check with gas utility company

7. Notify utility-install dirt trap in gas line

8. Locate source and correct

Removing and Replacing the Gas
Control Valve/Thermostat

Removing the Gas Control Valve/Thermostat:
1.

Turn the gas control/temperature knob to the “OFF”

position (Figure 19A).

2. Turn off the gas at the manual shut-off valve on the gas

supply pipe (Figure 3).

3.

Drain the water heater. Refer to the section on “Draining

and Flushing” and follow the procedure.

4.

Disconnect the igniter wire from the igniter lead wire.

Disconnect the temperature sensor wire, then use

needle nose pliers to disconnect the red (+) and white

(-) thermopile wires. Disconnect the pilot tube (7/16”

wrench) and manifold tube (3/4” wrench) at the gas

control valve/thermostat (Figure 22). Refer to “Gas

Piping” (Figure 3) and disconnect the ground joint union

in the gas piping. Disconnect the remaining pipe from

the gas control valve/thermostat.

5. To remove the gas control valve/thermostat, thread a 4”

section of gas pipe into the inlet and use it to turn the

gas control valve/thermostat (counterclockwise.) Do not

use a pipe wrench or equivalent to grip body. Damage

may result. Do not insert any sharp objects into the

inlet or outlet connections. Damage to the gas control

valve/thermostat may result.

Gas Control Valve/Thermostat:

To replace the gas control valve/thermostat, reassemble

in reverse order. When replacing the gas control valve/

thermostat, thread a 4” section of gas pipe into the inlet and

use it to turn the gas control valve/thermostat (clockwise.)

DO NOT OVER TIGHTEN, damage may result.

Be sure to use approved Teflon® tape or pipe joint

compound on the gas piping connections and fitting on

the back of the gas control valve that screws into the

tank.

Be sure to remove the pilot ferrule nut from the new gas

control valve/thermostat.

Turn the main gas supply on and check the gas supply

connections for leaks. Use an approved noncorrosive

leak detection solution. If such a solution is not available,

use a mixture of hand dish washing soap and water (one

part soap to 15 parts water) or childrens’ soap bubble

solution. Bubbles forming indicate a leak. Correct any

leak found.

Be sure tank is completely filled with water before

lighting and activating the water heater. Follow the

“Lighting Instructions” on page 17.

With the pilot and main burner lit, check the manifold

tube and pilot tube connections for leaks. Correct any

leak found.

If additional information is required, reference the

number on the cover of this manual for service

information.

TEFLON

®

is a registered trademark of E.I. Du Pont De Nemours and Company.

This manual is related to the following products: