beautypg.com

Vent pipe system, Draft hood installation – State Series 301 User Manual

Page 13

background image

13

ALTERNATIVE
OPENING
LOCATION

1 SQ. INCH
PER 3000 BTUH

CONFINED
SPACE

ALL AIR FROM OUTDOORS - USING A SINGLE PERMANENT OPENING

FIGURE 8B.

Vent Pipe System

This water heater uses a non-direct, single-pipe vent

system to remove exhaust gases created by the burning of

fossil fuels. Air for combustion is taken from the immediate

water heater location or is ducted in from the outside (see

“Combustion Air and Ventilation”).
This water heater must be properly vented for the removal

of exhaust gases to the outside atmosphere. Correct

installation of the vent pipe system is mandatory for the

proper and efficient operation of this water heater and is

an important factor in the life of the unit.
The vent pipe must be installed according to all local and

state codes or, in the absence of local and state codes, the

“National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current

edition. The vent pipe installation must not be obstructed

so as to prevent the removal of exhaust gases to the

outside atmosphere.
IMPORTANT: The use of vent dampers is not

recommended by the manufacturer of this water heater.

Although some vent dampers are certified by CSA

International, this certification applies to the vent damper

device only and does not mean they are certified for use

on this water heater.
U.L. recognized fuel gas and carbon monoxide (CO)

detectors are recommended in all applications and should

be installed using the manufacturer’s instructions and local

codes, rules, or regulations.
IMPORTANT: If you lack the necessary skills required

to properly install this venting system, you should not

proceed, but get help from a qualified technician.

Draft Hood Installation

SHEET METAL SCREWS (FOUR PROVIDED)

DRAFT HOOD

LEGS

LEGS

SLOT

SLOT

JACKET TOP

INSTALL THE DRAFT HOOD WITH
THE FOUR SCREWS PROVIDED.

FIGURE 9

GABLE VENT

TO OUTDOORS

INSTALL ABOVE

INSULATION

CONFINED

SPACE

ALTERNATE

AIR INLET

OUTLET

AIR TO

ATTIC 1 SQ.

INCH PER

4000 BTUH

INLET AIR FROM

THE CRAWL SPACE

OPEN

FOUNDATION

VENT

1 SQ. INCH PER

4000 BTUH

ALL AIR FROM OUTDOORS: INLET AIR FROM VENTILATED

CRAWL SPACE/OUTLET AIR TO VENTILATED ATTIC

FIGURE 6.

GABLE VENT
TO OUTDOORS

INSTALL ABOVE
INSULATION

CONFINED
SPACE

OUTLET AIR
TO ATTIC
1 SQ. INCH
PER 4000
BTUH

INLET AIR DUCT
1 SQ. INCH PER
4000 BTUH

12” MAXIMUM

ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC

FIGURE 7.

1 SQ. INCH PER
2000 BTUH

CONFINED
SPACE

1 SQ. INCH PER
2000 BTUH

INLET

OUTLET

OUTDOOR

AIR DUCTS

ALL AIR FROM OUTDOORS USING HORIZONTAL DUCTS

FIGURE 8A.

This manual is related to the following products: