Outback Power Systems FLEXmax 80 Quick Start Guide User Manual

Models, Features, Screen versions

background image

900-0134-01-00 Rev C.vsd\Overview\2013-01-17

©2012 OutBack Power Technologies. All Rights Reserved.

Page 1

In 23.2 V 0.0 A
Out 27.6 V 0.0 A

0.000 kW 0.0 kWH

AUX: OFF Sleeping

Charger Aux Light
EQ Misc Advanced
Logging Stats

EXIT

  GO

LCD Screen

Main Menu

Soft Key

Buttons

Soft Key

Commands

,

etc.

Navigation:

1

2

Advances to the
End-of-Day Screens

Advances to the
Main Menu Screens

IN 23.2 V 0.0 A
OUT 27.6 V 0.0 A

0.000 kW 0.0 kWH

AUX: OFF Sleeping

Status Screen

OutBack 24V

Power

Systems

Charge Controller

Startup Screen

NOTE: See the FLEXmax Series Owner’s Manual for details on
the settings available in the main menu.

PV Input Voltage

Battery Voltage

AUX Status

Instantaneous Kilowatts

PV Input Current
Output Current

Mode of Operation

Daily Accumulated
Kilowatt-hours

Select this option to proceed

Available menus

Adjusts the set points value

Switches between devices on the
ports of the Communications HUB

Soft Key Color Code:

Navigation colors

Selects a function (e.g., ON, OFF, AUTO)

NOTE: Soft key functions will vary depending on the selected
menu and are defined by the word above the key in the LCD.

If accompanied by a dashed
line, pressing that soft key will
return the user to the location
identified by the dashed line.
This will vary depending on the
devices in the system.

Indicates a 1-screen movement within a
menu. These are color-coded according to
their function or purpose.

Models:

FLEXmax 80: 80 amps maximum continuous
output current (up to 40°C without thermal derating)

FLEXmax 60: 60 amps maximum continuous
output current (up to 40°C without thermal derating)

Features:

Maximum Power Point Tracking

Supports 12, 24, 36, 48, and 60 Vdc
battery voltages

Backlit display screen (LCD) with 80 characters
(4 lines, 20 characters per line)

Last 128 days of operational data logging

Voltage step-down capability allowing a higher PV
array voltage configuration

Manual and automatic equalize cycles

Screen Versions:

English
Spanish
Australian
(English with different default settings)

FLEXmax Charge

Controller

PV

+

PV

BAT

BAT

+

MATE

Port

(RJ45)

RTS

Port

(RJ11)

Torque =

4 Nm (35 in-lb)

1

2

Terminals

LCD Screen

Soft Keys

IMPORTANT: Example only. Actual wiring may vary.
All configurations must comply with local and national
electric codes. Consult your local electric authority to
ensure compliance.

(RTS)

PV Combiner Box

Photovoltaic Array

(PV)

Negative

Positive

Ground

DC LEGEND

Battery Bank

Vented Battery Enclosure

DC Disconnect

Ground Bus

ON

OF

F

System Display

and Controller

(MATE3)

Maximum PV Input Wattage

per Charge Controller

Battery

Bank

Voltage

Maximum PV

Input Wattage

for the

FLEXmax 80

Maximum PV

Input Wattage

for the

FLEXmax 60

12 Vdc

1000 W

750 W

24 Vdc

2000 W

1500 W

36 Vdc

3000 W

2250 W

48 Vdc

4000 W

3000 W

60 Vdc

5000 W

3750 W