beautypg.com

V. troubleshooting guide, Ii. specifications – Aprilaire 1710A User Manual

Page 2

background image

Use the main control knob

(Figure 2) on the outside of the unit

to set the dehumidifier dryness setting. Start with a “NORMAL”

setting for most installations. Moving the knob clockwise to

“MORE” will make conditions drier. Moving the knob toward

“LESS” allows for higher moisture levels.
Based on the indoor temperature, use the following table to

determine the control knob setting to reach the desired RH value.

The dehumidifier will work to achieve these values.

ExAmPLE: At an indoor temperature of
75°F with a dehumidifier control knob
setting of 3, the dehumidifier will work to
achieve an RH value of 53%.
NOTES:
1. %RH values are ±5% and are to be

used as a GUIDE ONLY for initial
set-up.

2. Indoor Temperature is measured at the

inlet to the dehumidifier.

1. Install the drain line
NOTE:
The provided condensate trap must be installed to the dehumidifier.
• Verify the bottom of the dehumidifier is 2

1

/

2

” or higher above the floor.

• Insert the high side of the trap into the drain outlet (water flow direction is shown on the trap and

should point away from the dehumidifier)

• If there is not enough room to install the trap directly into the dehumidifier, use the provided 90°

elbow to position the trap close to the dehumidifier

ImPORTANT: The bottom of the trap outlet must be at least

1

/

2

inch below the bottom of the

dehumidifier to ensure a proper drainage slope (see

Figure 1).

• After verifying that the trap is in the proper orientation, use PVC primer and cement to secure the

trap in place. Cement the supplied threaded coupler to the outlet of the trap.

• Screw the supplied hose barb fitting into the coupler and attach the supplied

1

/

2

inch I.D. drain hose.

Route the hose to the nearest drain.

ImPORTANT: To prevent a pressure lock within the drain line, the tube mUST be installed with a

constant downward slope.

Prime the drain system by filling the drip pan in the dehumidifier with water until flow is completed to

the drain.
2. Plug the dehumidifier directly into an outlet – DO NOT USE AN ExTENSION CORD.
NOTE:
A 15 amp circuit is required for proper operation.
3. Turn the ON/OFF switch to ON.
4. System Checkout:
• Rotate the control knob clockwise to

the “Test” position.

a. The blower will start immediately

and after three minutes the

compressor will start.

b. Both will run for one minute then

both will shut off.

c. Turn the control knob to the

desired setting.

• If the unit does not run, refer to the

Troubleshooting guide.

V. TROUbLESHOOTINg gUIDE

SymPTOm

TROUbLESHOOTINg PROCEDURE / POSSIbLE REASON

Dehumidifier is producing hot air

• Reheat of outgoing air will cause a temperature increases across the dehumidifier

• Unit will possibly run continuously initially. After unit has “dried” home, dehumidifier

will cycle, reducing load

Dehumidifier not adequately dehumidifying

• Unit will need time to “dry” materials in home before effectively changing RH.

• Compressor is not turning on

• System undercharged

Dehumidifier is not draining properly

• Check condensate trap to be sure it is clear

• Check drain line for continuous slope

Dehumidifier does not run

• Follow all of the system checkout procedures. Make sure power switch is on!

• Check that circuit breaker is not tripped. The dehumidifier requires a minimum of

8 amps. The dehumidifier should be placed on its own dedicated 15 amp circuit

III. INSTALLATION INSTRUCTIONS

IV. OPERATINg INSTRUCTIONS

BARBED FITTING

COUPLER

TRAP

1/2”

2-1/2”

W

ATE

R FLOW

90-1393

FIgURE 1

Dimensions: 20

3

/

4

” W x 24” L x 20

3

/

8

”– 23

5

/

8

” H

Weight: 93 lbs.
Capacity: 90 pints per day @ 60%RH, 80˚F

(ANSI/AHAM DH-1-2003 standard conditions)
Power: 115 VAC, 8 Amps, Unit is equipped

with an 8 ft. grounded cord.

Design Airflow: 275 CFM @ 0.6 in. w.c.
Filter: MERV 8 Filter
Cabinet Insulation: 1” foil faced EPS insulation
Inlet Air Operating Conditions: 40˚F to 105˚F
Ambient Air Operation Conditions: 40˚F to 150˚F

II. SPECIFICATIONS

90-1327

FIgURE 2

%RH (± 5%) based on Control Knob Setting and Indoor Temperature

Control Knob

Setting

Indoor Temperature

65°F

70°F

75°F

80°F

1 – “LESS”

84%

71%

60%

2

86%

73%

61%

52%

3 – “noRMaL”

74%

63%

53%

45%

4 – “noRMaL”

64%

54%

45%

39%

5 – “noRMaL”

55%

46%

39%

33%

6

47%

39%

33%

28%

7 – “MoRE”

40%

34%

28%

24%

green LED

Activity

Status

ON Solid

Compressor ON

Blinking 1 second on, 1 second off

Sampling

Blinking 1/2 second ON, 1/2 second OFF

Defrosting

Test mode

At the end of test mode (3 minutes of DEH Fan + 1 minute of Compressor ON & DEH Fan), the Red and Green LEDs will turn ON

and OFF alternately until the knob has been turned away from “TEST”.

Red LED

Activity

Status

1 Blink every 5 seconds

There is an error with the RH sensor

2 Blinks every 5 seconds

The board temperature sensor is opened or shorted

3 Blinks every 5 seconds

The Model 70 Living Space Control fails to respond after 3 consecutive attempts

4 Blinks every 5 seconds

The refrigerant charge has been detected as low

5 Blinks every 5 seconds

The temperature sensor is out of the operating range

6 Blinks every 5 seconds

The internal frost sensor is opened or shorted

7 Blinks every 5 seconds

The float switch has opened

LED CODES