50 and 75 pound electric models – Alliance Laundry Systems TMB795C User Manual
Page 49
![background image](/manuals/39614/49/background.png)
Electrical Requirements
47
M414905
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
50 and 75 Pound Electric Models
NOTE: Wire size and breaker ratings were
obtained from the Canadian Electrical Code for
75 C. wire and are intended for use as a guideline
only. Electrical connections should be made by a
qualified electrical contractor in accordance with
all applicable local and national requirements.
NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
serial plate for most current specifications of
product being installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumbler must be
connected to its own individual branch circuit
breaker, not fuses, to avoid the possibility of “single
phasing” and causing premature failure of the
motor(s).
Serial Plate Rating
Terminal Block
Connections
Required
Serial Plate Amps
Recommended Circuit
Nonreversing
Reversing
Breaker
Rating
Wire Size
AWG (mm
2
)
240V/50Hz/1ph
(50 Pound only)
L1, Neutral and Ground
93
95
125A – 1 pole
1 (42.4)
200-208V/60Hz/3ph
L1, L2, L3 and ground
89
88
125A – 3 pole
1 (42.4)
200V/50Hz/3ph
L1, L2, L3 and ground
84
85
125A – 3 pole
1 (42.4)
230V/50Hz/3ph
L1, L2, L3 and ground
73
75
100A – 3 pole
3 (26.7)
240V/50Hz/3ph
L1, L2, L3 and ground
79
78
100A – 3 pole
3 (26.7)
240V/60Hz/3ph
L1, L2, L3 and ground
79
78
100A – 3 pole
3 (26.7)
380V/50 or 60Hz/3ph L1, L2, L3 and ground
47
48
60A – 3 pole
6 (13.3)
400-415V/50Hz/3ph
L1, L2, L3 and ground
43
44
60A – 3 pole
6 (13.3)
440V/60Hz/3ph
L1, L2, L3 and ground
41
41
51A – 3 pole
6 (13.3)
480V/60Hz/3ph
L1, L2, L3 and ground
38
38
50A – 3 pole
6 (13.3)
Table 10