Smart-UPS 750/1000/1500/2200/3000 VA 120/230 Vac Tower

10

Network Management Card Settings

These settings are available only on units that have a Network Management Card (NMC) and are set in
the factory. These settings can only be modified using an external interface, like the NMC web interface.

• NMC IP Address Mode

• NMC IP Address

• NMC Subnet Mask

• NMC Default Gateway

Function

Factory Default Options

Description

Name String
Outlet Group

Outlet Group 1

Edit these names using an external interface, such as the Network
Management Card Web interface.

UPS Name String UPS Outlets

Turn On Delay

0 sec

Set the value in
seconds

The amount of time the UPS or Switched Outlet
Group will wait between receiving the command
to turn on and the actual startup.

Turn Off Delay

0 sec

Set the value in
seconds

The amount of time that the UPS or Switched
Outlet Group will wait between receiving the
command to turn off and the actual shut down.

Reboot Duration 4 sec

Set the value in
seconds

The amount of time that the UPS or Switched
Outlet Group must remain off before it will
restart.

Minimum Return
Time

0 sec

Set the value in
seconds

The amount of battery runtime that must be
available before the UPS or Switched Outlet
Group will turn on.

Load Shed On
Battery

Disabled

• Shutdown with

Delay

• Shutdown

immediately

• Turn off

immediately

• Turn off with delay
• Disabled

When the unit switches to battery power, the UPS
can disconnect power to the Switched Outlet
Group to save runtime.

Configure this delay time, use the

L

OAD

S

HED

T

IME

WHEN

O

N

B

ATTERY

setting.

Load Shed Time
when On Battery

Disabled

Set the value in
seconds

The amount of time the outlets will function on
battery power before they will turn off.

Load Shed On
Runtime

Disabled

• Shutdown with

delay

• Shutdown

immediately

• Turn off

immediately

• Turn off with delay
• Disabled

When the battery runtime falls below the
specified value, the Switched Outlet Group will
turn off.

Configure this time using the

L

OAD

S

HED

R

UNTIME

R

EMAINING

setting.

Load Shed On
Runtime
Remaining

Disabled

Set the value in
seconds

When the remaining runtime reaches this level,
the Switched Outlet Group will turn off.

Load Shed on
Overload

Disabled

• Disabled
• Enabled

In the event of an overload (greater than 100%
output), the Switched Outlet Group will
immediately turn off to conserve power for
critical loads. The Switched Outlet Group will
only turn on again with a manual command.