0 specifications, 9 typical run time versus load – APC 2000 User Manual
Page 40

Page 38
9.0 Specifications
9.9 Typical run time versus load
Note:
Run times are typical at 25°C (77°F).
Load
900VA
model
1250VA
model
2000VA
model
Typical computer load
(0.7 volt-amps = Watts)
50 VA
150 min
290 min
450 min
Typical ASCII terminal
75 VA
125 min
250 min
400 min
Macintosh SE/30
100 VA
100 min
210 min
350 min
IBM PS/2 30 w/ monochrome monitor
150 VA
75 min
160 min
280 min
IBM PS/2 30 with VGA monitor
200 VA
58 min
120 min
220 min
IBM PS/2 55sx with VGA monitor
250 VA
44 min
90 min
180 min
Compaq 386/25e with VGA monitor
300 VA
36 min
70 min
145 min
Compaq 386/33 with VGA monitor
350 VA
28 min
50 min
109 min
IBM PS/2 80 file server
400 VA
24 min
38 min
88 min
Compaq 386/33 with 19" monitor
450 VA
20 min
32 min
70 min
Compaq 486/33 with 19" monitor
500 VA
18 min
27 min
55 min
Compaq Systempro server
550 VA
15 min
24 min
45 min
(2) Compaq 386/25e w/ VGA monitors
600 VA
13 min
22 min
40 min
(2) Compaq 386/33 with VGA monitors
700 VA
11 min
17 min
35 min
(2) IBM PS/2 80 file servers
800 VA
9 min
14 min
29 min
IBM AS/400 B20 minicomputer
900 VA
7 min
12 min
25 min
DEC MicroVax
1000 VA
10 min
22 min
(2) Compaq Systempro servers
1200 VA
7 min
17 min
(4) Compaq 386/33 w/ VGA monitors
1400 VA
14 min
1600 VA
11 min
(8) IBM PS/2 55sx w/ VGA monitors
2000 VA
8 min
(4) Compaq Systempro servers