beautypg.com

Wwarning, 24 connecting electric dryers – LG DLGX3361R User Manual

Page 24

background image

24

CONNECTING ELECTRIC DRYERS

(cont.)

Remove 3

1

2

inches (8.9 cm) of the outer

covering from the wire. Strip 1 inch (2.5 cm)

insulation from each wire. Bend the ends of

the three wires into a hook shape.

1

Remove the terminal block access cover

on the upper back of the dryer. Install a

UL-listed strain relief into the power cord

through-hole; then thread the power cable

prepared in Step 1 through the strain relief.

2

UL-Listed

Strain Relief

UL-Listed

3-Wire

Power Cord

Terminal

Block

Attach the two hot leads of the power cord

to the outer terminal block screws. Attach

the neutral wire to the center terminal block

screw. Connect the external ground (if

required by local codes) to the green ground

screw. TIGHTEN ALL SCREWS SECURELY.

Reinstall the terminal block access cover.

3

Ground Screw

Neutral

(White)

Hot

(Black)

Ground Wire

Hot

(Red)

1" (2.5 cm)

Three-Wire Connection for Electric Dryers: Direct Wire

• A 3-wire connection is NOT permitted on new

construction after January 1, 1996.

• A UL-listed strain relief is required.

• Use UL-listed

3-wire #10 AWG-minimum

copper conductor cable.

• Allow at least 5 ft. (1.5 m) length to allow for

removal and reinstallation of the dryer.

w

WARNING:

•Connect the power cord to the terminal block. Each colored wire should be connected

to same color screw. Wire color indicated on manual is connected to the same color

screw in block. Failure to follow these instructions may result in a short or overload.

•Grounding through the neutral conductor is prohibited for: (1) new branch-circuit

installations, (2) mobile homes, (3) recreational vehicles, and (4) areas where local

codes prohibit grounding through the neutral conductor.

USA ONLY

MFL62512833_EN_101008.indd 24

10/8/10 4:54:48 PM

This manual is related to the following products: