18 ACS 3216 Operators Manual
S A F E
SAFE OUTPUT POWER
To set the output level in a sensor break (open
circuit) condition
-100.0 to 100.0% limited by OP.HI and OP.LO
0.0%
L3
none
Transfer between Auto/Manual/Auto is
bumpless
SteP
Transfer from Auto to Manual, the output
goes to a pre-set value (F.OP)
F . M O D
FORCED MANUAL OUTPUT MODE
Selects how the loop behaves on transfer from
Auto to Manual.
Transfer from Manual to Auto is always
bumpless.
Last
Transfer from Auto to Manual, the output
goes to the previously set manual value
none
L3
Lin
Linear
OIL
Oil cooling
H20
Water cooling
C o o l . t
NON-LINEAR COOLING TYPE
This selects an algorithm most suited to the
type of cooling. Typically used in extruders.
Fan
Forced air cooling
As order
code
Conf
F . O P
FORCED OUTPUT
To pre-set a value for the Manual output
when F.MOD = STEP
-100.0 to 100.0% limited by OP.HI and OP.LO
0.0
L3
Auto
To select automatic operation
Man
To select manual operation
A - M
LOOP MODE – AUTO MANUAL OFF
OFF
Control outputs inhibited
L3
No
l b r
LOOP BREAK STATUS
YES
Shows the current status of loop break.
Read only
ALARM LIST
‘ALARM’
Name
Scrolling Display
Parameter Description
Value
Default
Access
Level
none
Alarm not configured
Hi
Full Scale High
Lo
Full Scale Low
d.Hi
Deviation High
d.Lo
Deviation Low
A1.TYP
ALARM 1 TYPE
Selects the type of alarm
bnd
Deviation band
As order
code
Conf
A 1 . - - -
ALARM 1 SETPOINT
Alarm 1 threshold value.
The last three characters show the type of
alarm configured from the above list
Instrument range
0
L3
OFF
Alarm off
A 1 . s t s
ALARM 1 OUTPUT
Indicates the status of the alarm
On
Alarm on
Read
only
A1.HYS
ALARM 1
HYSTERESIS
See description in manufacture manual
0 to 9999
Conf
none
Non-latching
Auto
Latching with automatic
resetting
Man
Latching with manual
resetting
A1.LAT
ALARM 1
LATCHING TYPE
See description in manufacture manual
Evt
Event (no alarm flashing
beacon but messages can
be displayed)
As order
code
Conf
No
No blocking
A1.BLK
ALARM 1
BLOCKING
See description in manufacture manual
yes
Blocking
No
Conf
The above parameters are repeated for Alarm 2, A2; Alarm 3, A3; Alarm 4, A4
TIMER
LIST
‘t i m e r ’’
Name
Scrolling
Display
Parameter Description
Value
Default
Access
Level
none
Timer disabled
dwel
Dwell
deLY
Delayed switch on
SFST
Soft start
T M . C F G
TIMER
CONFIGURAT
ION
Timer type configuration
prog
Programmer
As order
code
L3
Hour
Hours
HH:MM
T M . r e s
TIMER
RESOLUTION
To set the time units
Min
Minutes
MM:SS
Conf
R/O
L3