A.O. Smith BPD-400 User Manual

Page 11

background image

11

FIGURE 9

WIRE FENCE

When the water heater outlet terminal is low enough to be touched
accidentally, or is accessible to small children, a wire mesh chain link
fence (as shown in Figure 9) may be used. Care should be taken to
maintain adequate ventilation around the outlet terminal. If a chain link
fence is installed, it must not be used as a storage area for items that
may block proper ventilation.

FIGURE 9

WARNING

THE LOCATION SELECTED MUST PROVIDE CLEARANCES FOR SERVICING
AND PROPER OPERATION OF THE WATER HEATER.

WARNING

VENT TERMINATION MUST NOT BE WITHIN 4 FEET OF ANY ITEMS SUCH AS GAS
METERS, GAS VALVES OR OTHER GAS REGULATING EQUIPMENT.

WARNING

FAILURE TO HAVE REQUIRED CLEARANCES BETWEEN WATER HEATER
AND COMBUSTIBLE MATERIAL WILL RESULT IN A FIRE HAZARD.

FIGURE 7

FACTS TO CONSIDER ABOUT THE LOCATION

VENTING THROUGH ROOF-CLEARANCES

• 1" (2.5 cm) clearance for 4" or 6" PVC or CPVC piping from

combustible surfaces for outlet piping.

• 0" clearance for 4" or 6" PVC or CPVC piping from combustible

surfaces for inlet piping.

• The Power Direct Vent inlet and outlet terminals shall terminate at

least 18" (46 cm) above the roof surface. See Figure 10.

• The venting system must be installed in a manner which allows

inspection of the installation of the venting pipes and joints as well as
periodic inspection after installation as required by ANSI Standards.

FIGURE 8 - DIRECT VENT TERMINAL CLEARANCES - US INSTALLATION