beautypg.com

Ar ch ive d – Seametrics FT520-84 v.1 User Manual

Page 3

background image

3 of 4

Connections

Set Pulse Out. An output pulse is activated at the
selected volume intervals if this feature is in use.
Otherwise, it does not need to be set.

Set 20 mA Out. A 4-20 mA analog output is standard
on this unit. If a 4-20 mA current loop is connected, set
the flow rate, in the desired units, at which the peak 20
mA is desired. The controller will automatically scale the
4 mA output to zero flow.

Set Regeneration Volume. This is the volume (in the
units you have selected, typically gallons) at which the
relay energizes to initiate a regeneration cycle. Set to
the desired amount using the

and

keys.

Set Regeneration Time. This is the length of time, in
seconds that the relay remains energized to initiate
regeneration. Using the

key, set for a bit over the

minimum time required by the regeneration valve to begin
a cycle.

Set Relay Mode. Choose between single relay (Relay
No. 1) and dual relay (Alternate Relays) operation, using
the

key. In alternate relay mode, the first regeneration

will use relay 1, and the next will use relay 2, and so on.

Clear Total. This function resets the running total back

to zero. It is unrelated to the regeneration function, and
can be ignored unless it is needed. To reset to zero,
press

and

simultaneously, as instructed.

Operation

Choice of Displays. When all of the settings have been
entered, the next press of the Set key puts the unit in
operation. If a T appears at the left side of the display,
the values shown are flow rate and running total. If there
is no T, the values shown are flow rate and units
remaining until regeneration. The total increases with
flow, and the regeneration quantity counts down. Use
the

key to choose the preferred display, usually

regeneration quantity.

Regeneration Initiation. When the regeneration quantity
number first reaches 0, relay 1 energizes for the length
of time which has been set. The regeneration quantity
immediately resets to its setting and begins counting
down again. If alternating mode has been selected, the
next time it reaches 0, relay 2 will energize, and the cycle
after that returns to relay 1.

Pulse 1

Alternate

low-voltage power

12-24 VDC

Pulse 2

Relay 2

Relay 1

NC
COM

NO
NC

NO

COM

Regeneration

Initiation

Line

Neutral

Ground

Resume

0-10 V

Sensor input

Analog
Outputs

4-20 mA

External Power

Internal Power

Start/Stop

+

– +

s1

+

s2

RESUME

COM

REGENERATION

Remote
Controls

Pulse Outputs

(for metering pumps)

Main

power fuse

250 mA

DC Power fuse
1 Amp

Power

loop power

jumper

Ribbon connector

from display board

Meter

Ground

Power signal

RED

WHITE

BLACK

Dry contact

+

Relay Pulse

10 Amp

AR

CH

IVE

D