beautypg.com

Compressed air supply air pressure – American Dryer Corp. AD-81 III User Manual

Page 27

background image

113159-2

www.amdry.com

23

d. Shutoff valves for each dryer should be installed in the supply, return, and drip trap return lines. This

will allow the dryer to be isolated from the supply and return mains if the dryer needs maintenance
work.

e. Install an inverted bucket steam trap and check valve for each unit at least 12-inches (30.48 cm) below

steam coil as close to the coil as possible. A trap with a capacity of 1,000 lbs (454 kg) of condensate per
hour at 125 psi (8.62 bar) is needed for each unit.

f. A vacuum breaker should be installed for each unit in the piping. This will prevent the condensing

steam from causing a vacuum inside the coil and possibly damaging the coil.

g. The supply and return lines should be insulated. This will save energy and provide for the safety of the

operator and maintenance personnel.

h. Water pockets in the supply line, caused by low points, will provide wet steam to the coil possibly

causing coil damage. ALL horizontal runs of steam supply piping should be pitched 1/4-inch
(6.35 mm) for every 1 foot (0.30 meters) back towards the steam supply header causing any condensate
in the line to drain to the header. Install a bypass trap in any low point to eliminate wet steam.

IMPORTANT: Flexible hoses and couplings must be used. Coil failure due to hard plumbing

connections will VOID THE WARRANTY.

3. Steam Damper Air System Connections

This dryer is manufactured with a pneumatic (piston) damper system, which requires an external supply of
compressed air. The air connection is made to the steam damper solenoid valve, which is located at the
rear inner top area of the dryer just above the electric service relay box.

a. Air Requirements

Shaded areas are stated in metric equivalents

Compressed

Air Supply

Air Pressure

Normal

80 psi

5.51 bar

Minimum Supply

70 psi

4.82 bar

Maximum Supply

90 psi

6.21 bar